xupsControlToBypassDelay

XUPS-MIB · .1.3.6.1.4.1.534.1.9.5

Object

scalar r/w seconds Integer32
Setting this value to other than zero will cause the UPS
output to go to Bypass after the number of seconds.
If the Bypass is unavailable, this may cause the UPS
to not supply power to the load.
Setting it to 0 will cause an attempt to abort a pending
shutdown.

Context

MIB
XUPS-MIB
OID
.1.3.6.1.4.1.534.1.9.5
Type
scalar
Access
readwrite
Status
current
Units
seconds
Parent
xupsControl
Siblings
6

Syntax

seconds Integer32

Values & Constraints

Object Constraints
range: 0-2147483647

Related Objects