xupsBatteryAbmStatus
XUPS-MIB ·
.1.3.6.1.4.1.534.1.2.5
Object
scalar
Enumeration
Gives the status of the Advanced Battery Management and Battery state; batteryFloating(3) status means that the charger is temporarily charging the battery to its float voltage; batteryResting(4) is the state when the battery is fully charged and none of the other actions (charging/discharging/floating) is being done. checkBattery(8) indicates that the Battery state is uncertain following a poor battery test result.
Context
- MIB
- XUPS-MIB
- OID
.1.3.6.1.4.1.534.1.2.5- Type
- scalar
- Access
- readonly
- Status
- current
- Parent
- xupsBattery
- Siblings
- 9
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | batteryCharging |
2 | batteryDischarging |
3 | batteryFloating |
4 | batteryResting |
5 | unknown |
6 | batteryDisconnected |
7 | batteryUnderTest |
8 | checkBattery |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| xupsBatTimeRemaining Battery run time in seconds before UPS turns off due
to low battery. | scalar | seconds Integer32 | .1.3.6.1.4.1.534.1.2.1 |
| xupsBatteryLowCapacity Indicates if the battery capacity is below the threshold set in the UPS. | scalar | Enumeration | .1.3.6.1.4.1.534.1.2.10 |
| xupsBatVoltage Battery voltage as reported by the UPS meters. | scalar | Volts DC Integer32 | .1.3.6.1.4.1.534.1.2.2 |
| xupsBatCurrent Battery Current as reported by the UPS metering.
Current is positive when discharging, negative
when recharging the battery. | scalar | Amps DC Integer32 | .1.3.6.1.4.1.534.1.2.3 |
| xupsBatCapacity Battery percent charge. | scalar | percent Integer32 | .1.3.6.1.4.1.534.1.2.4 |
| xupsBatteryLastReplacedDate The date when the Batteries in this UPS were last replaced. Free text format,
so the preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc). | scalar | OctetString | .1.3.6.1.4.1.534.1.2.6 |
| xupsBatteryFailure Indicates if a battery fault detected or battery tests failed. | scalar | Enumeration | .1.3.6.1.4.1.534.1.2.7 |
| xupsBatteryNotPresent Indicates if the UPS has no battery either internal or external. | scalar | Enumeration | .1.3.6.1.4.1.534.1.2.8 |
| xupsBatteryAged Indicates if the battery is over aged. | scalar | Enumeration | .1.3.6.1.4.1.534.1.2.9 |