upsSmartConfigLowBatteryRunTime

XPPC-MIB · .1.3.6.1.4.1.935.1.1.1.5.2.8

Object

scalar mandatory r/w Integer32
The desired run time in seconds once the low battery
condition is reached.  Allowed values are 120, 300, 420,
or 600 seconds.  During this time the UPS will produce a
constant warning tone which can not be disabled.
                          
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value.  If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used.