upsSmartConfigHighTransferVolt

XPPC-MIB · .1.3.6.1.4.1.935.1.1.1.5.2.2

Object

scalar mandatory r/w Integer32
The maximum line voltage in 1/10 VAC allowed before the
UPS system transfers to battery backup.
                          
Allowed value depend on the UPS used:
120 Volt units allow settings of 1290, 1320, 1350, 1380.
100 Volt units allow settings of 1080, 1100, 1120, 1140.
230 Volt units allow settings of 2530, 2640, 2710, 2800.
208 Volt units allow settings of 2240, 2290, 2340, 2390.
                          
If a value other than a supported value is provided in a
set request, the UPS interprets it as the next lower
acceptable value.  If the provided value is lower than
the lowest acceptable value, the lowest acceptable
value is used.