wtWebioAn1GraphPtAlarmTimerCron
WebGraph-OLD-Thermometer-PT-US-MIB ·
.1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.30
Object
column
mandatory
r/w
OctetString
This entry defines a time window for alarm 1-8 and a activation time for the report.
A time window is definied by start and stop time stamp, seperated by a space or tab.
The activation time of the report is defined by a single start time stamp.
Each time stamp contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger an action, weekday and day of month
are interpreted separatley.
1: Minutes Range 0-59
2. Hours Range 0-23, 0 is midnight
3: Day of month Range 1-31
4: Month Range 1-12
5: Weekday Range 0-6, 0 is sunday
Syntax for every field:
- an asterix (*) enables every possible setting of a field
- single numbers seperated by commas (i.e.: 2,14,22)
- a partition within the allowed range (i.e.: 1-5)
- step size within a partition of the allowed range (i.e.: 0-59/2 every second minute).
Context
- MIB
- WebGraph-OLD-Thermometer-PT-US-MIB
- OID
.1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.30- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- wtWebioAn1GraphPtAlarmEntry
- Table
- wtWebioAn1GraphPtAlarmTable
- Siblings
- 32
Syntax
OctetString
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| wtWebioAn1GraphPtAlarmTrigger mandatory Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3:
Bit 0 : Timer
Bit 1 : ColdStart
Bit 2 : WarmStart
Bit 3 : Sensor lost
Bit 4-7: unused
… | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.1 |
| wtWebioAn1GraphPtAlarmMailText mandatory Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.10 |
| wtWebioAn1GraphPtAlarmManagerIP mandatory Name or IP address of the SNMP Manager which accepts the trap. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.11 |
| wtWebioAn1GraphPtAlarmTrapText mandatory This text is sent in the trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.12 |
| wtWebioAn1GraphPtAlarmMailOptions mandatory Binary coded options:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Attach Thermo.csv Enable
Bit 1 : CSV-Data_since_last_report
Bit 2-7: unused | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.13 |
| wtWebioAn1GraphPtAlarmTcpIpAddr mandatory Name or IP address of the TCP server which accepts the trap. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.14 |
| wtWebioAn1GraphPtAlarmTcpPort mandatory Port number of the TCP server which accepts the trap. | column | Integer32 | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.15 |
| wtWebioAn1GraphPtAlarmTcpText mandatory This text is sent in the TCP trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.16 |
| wtWebioAn1GraphPtAlarmClearMailSubject mandatory Subject line for alarm clear mail. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.17 |
| wtWebioAn1GraphPtAlarmClearMailText mandatory Alarm clear mail text: <Tn> provides the current temperature; n = 1..8. <Z> provides the current time. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.18 |
| wtWebioAn1GraphPtAlarmClearTrapText mandatory This text is sent in the trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.19 |
| wtWebioAn1GraphPtAlarmMin mandatory Minimum temperature in degrees with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.2 |
| wtWebioAn1GraphPtAlarmClearTcpText mandatory This text is sent in the TCP trap body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.20 |
| wtWebioAn1GraphPtAlarmSyslogIpAddr mandatory IP address of the syslog server to which the Webio device should send syslog messages. | column | RFC1155-SMIIpAddress | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.21 |
| wtWebioAn1GraphPtAlarmSyslogPort mandatory Port number of the syslog server to which the Webio device should send syslog messages. | column | Integer32 | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.22 |
| wtWebioAn1GraphPtAlarmSyslogText mandatory Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.23 |
| wtWebioAn1GraphPtAlarmSyslogClearText mandatory Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.24 |
| wtWebioAn1GraphPtAlarmFtpDataPort mandatory Local data port: 1..65535 or AUTO: the next free port will be assigned. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.25 |
| wtWebioAn1GraphPtAlarmFtpFileName mandatory Name of the file including path informations. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.26 |
| wtWebioAn1GraphPtAlarmFtpText mandatory Message text to store on the FTP server. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.27 |
| wtWebioAn1GraphPtAlarmFtpClearText mandatory Alarm clear message to store on the FTP server. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.28 |
| wtWebioAn1GraphPtAlarmFtpOption mandatory Binary coded options, select only one option at the same time:
STORE = replace file
APPEND = append message at the end of the file
Octet 1: unused
Octet 2: unused
… | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.29 |
| wtWebioAn1GraphPtAlarmMax mandatory Maximum temperature in degrees with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.3 |
| wtWebioAn1GraphPtAlarmDeltaTemp mandatory Maximum rate of change degrees/min with maximum 2 decimal places.
Compared with the average of a period of 5 minutes. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.31 |
| wtWebioAn1GraphPtAlarmName mandatory Alert name | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.39 |
| wtWebioAn1GraphPtAlarmHysteresis mandatory Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.4 |
| wtWebioAn1GraphPtAlarmActive mandatory Alert active
1 = ON
0 = OFF | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.40 |
| wtWebioAn1GraphPtAlarmDelay mandatory Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes). | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.5 |
| wtWebioAn1GraphPtAlarmInterval mandatory Send interval for alarm messages. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.6 |
| wtWebioAn1GraphPtAlarmEnable mandatory Binary coded alarm enable:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Mail Enable
Bit 1 : SNMP Trap enable
Bit 2 : TCP Client enable
Bit 3 : Syslog … | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.7 |
| wtWebioAn1GraphPtAlarmEMailAddr mandatory E-Mail address for sending the alarm mail to. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.8 |
| wtWebioAn1GraphPtAlarmMailSubject mandatory Subject line for alarm mail. | column | OctetString | .1.3.6.1.4.1.5040.1.2.17.3.1.5.3.1.9 |