pduPhaseRealPower
VERTIV-IMD-MIB ·
.1.3.6.1.4.1.21239.5.2.3.2.1.12
Object
column
watts Unsigned32
Real power for phase in watts
Context
- MIB
- VERTIV-IMD-MIB
- OID
.1.3.6.1.4.1.21239.5.2.3.2.1.12- Type
- column
- Access
- readonly
- Status
- current
- Units
- watts
- Parent
- pduPhaseEntry
- Table
- pduPhaseTable
- Siblings
- 14
Syntax
watts Unsigned32
Values & Constraints
Object Constraints
range: 0-9999
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pduPhaseIndex Table entry index value | column | Integer32 | .1.3.6.1.4.1.21239.5.2.3.2.1.1 |
| pduPhaseCurrentMin Lowest RMS current measured on this phase, since power-up or last reset. The value is given in hundreths of an amp. | column | centiamps (rms) Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.2.1.10 |
| pduPhaseCurrentPeak Highest instantaneous current measured on ths phase, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all platforms, due to ha… | column | centiamps Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.2.1.11 |
| pduPhaseApparentPower Apparent power for phase in volt-amps | column | volt-amps Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.2.1.13 |
| pduPhasePowerFactor Power factor for phase | column | % Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.2.1.14 |
| pduPhaseEnergy Accumulated energy for phase in watt-hours | column | watt-hours Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.2.1.15 |
| pduPhaseName PDU phase name (factory-assigned) | column | OctetString | .1.3.6.1.4.1.21239.5.2.3.2.1.2 |
| pduPhaseLabel PDU phase label (user-defined) | column | OctetString | .1.3.6.1.4.1.21239.5.2.3.2.1.3 |
| pduPhaseVoltage PDU phase voltage in tenths of a volt | column | decivolts (rms) Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.2.1.4 |
| pduPhaseVoltageMax Highest RMS voltage measured on this phase, since power-up or last reset. The value is given in tenths of a volt | column | decivolts (rms) Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.2.1.5 |
| pduPhaseVoltageMin Lowest RMS voltage measured on this phase, since power-up or last reset. The value is given in tenths of a volt | column | decivolts (rms) Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.2.1.6 |
| pduPhaseVoltagePeak Highest instantaneous voltage measured on this phase, since power-up or last reset. The value is given in tenths of a volt. This object may not exist on all platforms, due to har… | column | decivolts Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.2.1.7 |
| pduPhaseCurrent PDU phase current reading in hundreths of an amp. | column | centiamps (rms) Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.2.1.8 |
| pduPhaseCurrentMax Highest RMS current measured on this phase, since power-up or last reset. The value is given in hundreths of an amp. | column | centiamps (rms) Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.2.1.9 |