pduLineCurrentMin
VERTIV-IMD-MIB ·
.1.3.6.1.4.1.21239.5.2.3.4.1.6
Object
column
centiamps (rms) Unsigned32
Lowest RMS current measured on this line, since power-up or last reset. The value is given in hundreths of an amp.
Context
- MIB
- VERTIV-IMD-MIB
- OID
.1.3.6.1.4.1.21239.5.2.3.4.1.6- Type
- column
- Access
- readonly
- Status
- current
- Units
- centiamps (rms)
- Parent
- pduLineEntry
- Table
- pduLineTable
- Siblings
- 6
Syntax
centiamps (rms) Unsigned32
Values & Constraints
Object Constraints
range: 0-9900
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pduLineIndex Table entry index value | column | Integer32 | .1.3.6.1.4.1.21239.5.2.3.4.1.1 |
| pduLineName PDU line name (factory-assigned) | column | OctetString | .1.3.6.1.4.1.21239.5.2.3.4.1.2 |
| pduLineLabel PDU line label (user-defined) | column | OctetString | .1.3.6.1.4.1.21239.5.2.3.4.1.3 |
| pduLineCurrent PDU line current reading in hundreths of an amp | column | centiamps (rms) Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.4.1.4 |
| pduLineCurrentMax Highest RMS current measured on this line, since power-up or last reset. The value is given in hundreths of an amp. | column | centiamps (rms) Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.4.1.5 |
| pduLineCurrentPeak Highest instantaneous current measured on this line, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all platforms, due to ha… | column | centiamps Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.4.1.7 |