pduBreakerLabel
VERTIV-IMD-MIB ·
.1.3.6.1.4.1.21239.5.2.3.3.1.3
Object
column
r/w
OctetString
PDU breaker label (user-defined)
Context
- MIB
- VERTIV-IMD-MIB
- OID
.1.3.6.1.4.1.21239.5.2.3.3.1.3- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- pduBreakerEntry
- Table
- pduBreakerTable
- Siblings
- 6
Syntax
OctetString
Values & Constraints
Object Constraints
range: 0-25
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pduBreakerIndex Table entry index value | column | Integer32 | .1.3.6.1.4.1.21239.5.2.3.3.1.1 |
| pduBreakerName PDU breaker name (factory-assigned) | column | OctetString | .1.3.6.1.4.1.21239.5.2.3.3.1.2 |
| pduBreakerCurrent PDU breaker current reading in hundreths of an amp | column | centiamps (rms) Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.3.1.4 |
| pduBreakerCurrentMax Highest RMS current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp. | column | centiamps (rms) Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.3.1.5 |
| pduBreakerCurrentMin Lowest RMS current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp. | column | centiamps (rms) Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.3.1.6 |
| pduBreakerCurrentPeak Highest instantaneous current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all platforms, due to… | column | centiamps Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.3.1.7 |