a2dSensorEntry
VERTIV-IMD-MIB ·
.1.3.6.1.4.1.21239.5.2.11.1
Object
row
Entry in the a2dSensorTable table: each entry contains an index and other sensor details
Context
- MIB
- VERTIV-IMD-MIB
- OID
.1.3.6.1.4.1.21239.5.2.11.1- Type
- row
- Status
- current
- Parent
- a2dSensorTable
- Table
- a2dSensorTable
- Children
- 13
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| a2dSensorIndex Table entry index value | column | Integer32 | .1.3.6.1.4.1.21239.5.2.11.1.1 |
| a2dSensorMax Maximum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), t… | column | Integer32 | .1.3.6.1.4.1.21239.5.2.11.1.10 |
| a2dSensorLowLabel Label for 0 (low) binary value. This field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. O… | column | OctetString | .1.3.6.1.4.1.21239.5.2.11.1.11 |
| a2dSensorHighLabel Label for 1 (high) binary value. The field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. O… | column | OctetString | .1.3.6.1.4.1.21239.5.2.11.1.12 |
| a2dSensorAnalogLabel Label for the analog measurement | column | OctetString | .1.3.6.1.4.1.21239.5.2.11.1.13 |
| a2dSensorSerial Serial Number | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.21239.5.2.11.1.2 |
| a2dSensorLabel User-defined label | column | OctetString | .1.3.6.1.4.1.21239.5.2.11.1.3 |
| a2dSensorAvail Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable | column | SNMPv2-SMIGauge32 | .1.3.6.1.4.1.21239.5.2.11.1.4 |
| a2dSensorValue Analog measurement value, within either a user-defined or preset range, depending on a2dSensorMode. | column | Integer32 | .1.3.6.1.4.1.21239.5.2.11.1.5 |
| a2dSensorDisplayValue For current/voltage modes, the analog value is given as a string. In binary modes, the value is either a2dSensorLowLabel or a2dSensorHighLabel, based on a2dSensorValue. | column | OctetString | .1.3.6.1.4.1.21239.5.2.11.1.6 |
| a2dSensorMode Binary modes have two states represented by the values 0 (low) or 1 (high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel. Current and voltage modes provide a scale… | column | Enumeration | .1.3.6.1.4.1.21239.5.2.11.1.7 |
| a2dSensorUnits The units for the analog value. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fixed, based on mode. | column | OctetString | .1.3.6.1.4.1.21239.5.2.11.1.8 |
| a2dSensorMin Minimum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), t… | column | Integer32 | .1.3.6.1.4.1.21239.5.2.11.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| a2dSensorIndex Table entry index value | column | Integer32 | .1.3.6.1.4.1.21239.5.2.11.1.1 |