upsWellKnownAlarms
SOCOMECUPS7-MIB ·
.1.3.6.1.4.1.4555.1.1.7.1.6.3
Object
node
No description available.
Context
- MIB
- SOCOMECUPS7-MIB
- OID
.1.3.6.1.4.1.4555.1.1.7.1.6.3- Type
- node
- Parent
- upsAlarm
- Siblings
- 2
- Children
- 62
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAlarmsPresent mandatory The present number of active alarm conditions. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.1 |
| upsAlarmTable mandatory A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at… | table | - | .1.3.6.1.4.1.4555.1.1.7.1.6.2 |
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAlarmImminentStop mandatory UPS in imminent stop. Load will switch off. (A000) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.1 |
| upsAlarmRemoteService mandatory The UPS requests a remote service action. (A013) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.10 |
| upsAlarmGeneralFault mandatory A general fault in the UPS has been detected.
One of UPS alarm is present. (A015) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.11 |
| upsAlarmBatteryCircuitOpen mandatory Battery circuit open. Battery breaker or fuse open. (A016) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.12 |
| upsAlarmBatteryDischarged mandatory The UPS will be unable to sustain the present load
when and if the utility power is lost.
The Battery is discharched. (A017) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.13 |
| upsAlarmLowBattery mandatory The remaining battery run-time is less than or equal
to battery low threshold. (A018) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.14 |
| upsAlarmOnBattery mandatory The UPS is drawing power from the batteries. (A019) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.15 |
| upsAlarmBatteryTemperature mandatory Battery Temperature Alarm. (A020) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.16 |
| upsAlarmBatteryRoom mandatory An external alarm has been detected in the Battery room.
This alarm depends on external sensor: gaz, temperature,
humidity or dry-contact. (A021) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.17 |
| upsAlarmBatteryTest mandatory The battery has been detected as weak during the test. (A022) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.18 |
| upsAlarmBatteryFault mandatory One or more batteries have been determined to require replacement. (A027) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.19 |
| upsAlarmOverload mandatory The output load exceeds the UPS output capacity. (A001) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.2 |
| upsAlarmRectifierFault mandatory Rectifier Critical alarm. (A032) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.20 |
| upsAlarmRectifierAlarm mandatory Rectifier Preventive alarm. (A033) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.21 |
| upsAlarmRecInputBad mandatory rectifier Input power supply is out of tolerance or absent. (A035) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.22 |
| upsAlarmGenSetGeneral mandatory Gen-set general alarm.
coming from external dry-contact. (A036) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.23 |
| upsAlarmBatteryChargerFault mandatory Battery charger Critical Alarm. (A037) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.24 |
| upsAlarmBatteryChargerAlarm mandatory Battery charger Preventive Alarm. (A038) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.25 |
| upsAlarmInverterFault mandatory Inverter Critical alarm. (A040) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.26 |
| upsAlarmInverterAlarm mandatory Inverter preventive alarm. (A041) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.27 |
| upsAlarmBypassFault mandatory Inverter Critical alarm. (A048) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.28 |
| upsAlarmBypassAlarm mandatory Inverter preventive alarm. (A049) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.29 |
| upsAlarmTemperature mandatory UPS temperature is out of tolerance. (A002) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.3 |
| upsAlarmBypInputBad mandatory Bypass Input power supply is out of tolerance or absent. (A050) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.30 |
| upsAlarmPhaseRotationFault mandatory Phase rotation fault. (A051) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.31 |
| upsAlarmFansFailure mandatory Fans failure. (A054) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.32 |
| upsAlarmMaintenanceBypass mandatory Maintenance bypass alarm.
Output breaker and manual bypass breaker closed together. (A056) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.33 |
| upsAlarmUPSPowerOffActive mandatory UPS power off has been activated by external device. (A059) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.34 |
| upsAlarmWrongConfiguration mandatory Configuration data map corrupted, or wrong configuration. (A060) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.35 |
| upsAlarmInternalFailure mandatory Internal failure, or internal communication failure. (A061) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.36 |
| upsAlarmOptionalBoards mandatory Optional boards alarm.
Board not present or wrong configuration (A062) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.37 |
| upsAlarmExternalAlarm1 mandatory External Alarm 1.
Coming from ADC Card: Input set as alarm (A064) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.38 |
| upsAlarmExternalAlarm2 mandatory External Alarm 2.
Coming from ADC Card: Input set as alarm (A065) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.39 |
| upsAlarmTransferLock mandatory Automatic and manual transfer are locked. (A003) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.4 |
| upsAlarmExternalAlarm3 mandatory External Alarm 3.
Coming from ADC Card: Input set as alarm (A066) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.40 |
| upsAlarmExternalAlarm4 mandatory External Alarm 4.
Coming from ADC Card: Input set as alarm (A067) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.41 |
| upsAlarmModule1Alarm mandatory Unit or Module 1 in parallel general alarm. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.42 |
| upsAlarmModule2Alarm mandatory Unit or Module 2 in parallel general alarm. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.43 |
| upsAlarmModule3Alarm mandatory Unit or Module 3 in parallel general alarm. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.44 |
| upsAlarmModule4Alarm mandatory Unit or Module 4 in parallel general alarm. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.45 |
| upsAlarmModule5Alarm mandatory Unit or Module 5 in parallel general alarm. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.46 |
| upsAlarmModule6Alarm mandatory Unit or Module 6 in parallel general alarm. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.47 |
| upsAlarmModule7Alarm mandatory Unit or Module 7 in parallel general alarm. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.48 |
| upsAlarmModule8Alarm mandatory Unit or Module 8 in parallel general alarm. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.49 |
| upsAlarmAutoTransferImpossible mandatory Automatic transfer is disabled.
Inverter and bypass sources are not synchronized (A004) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.5 |
| upsAlarmModule9Alarm mandatory Unit or Module 9 in parallel general alarm. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.50 |
| upsAlarmModule10Alarm mandatory Unit or Module 10 in parallel general alarm. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.51 |
| upsAlarmModule11Alarm mandatory Unit or Module 11 in parallel general alarm. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.52 |
| upsAlarmModule12Alarm mandatory Unit or Module 12 in parallel general alarm. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.53 |
| upsAlarmAutoTestRunning mandatory The UPS has launched the auto-test. (S030) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.54 |
| upsAlarmOnBypass mandatory Load supplied by automatic bypass.
Load not protected. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.55 |
| upsAlarmUpsOutputOff mandatory The output of the UPS is in the off state.
Load OFF or UPS on standby mode. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.56 |
| upsAlarmUpsSystemOff mandatory The UPS system is in the off state.
Rectifier and Inverter are off. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.57 |
| upsAlarmCommunicationLost mandatory The communication with UPS has been lost. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.58 |
| upsAlarmShutdownPending mandatory The condition to shutdown servers has been detected.
The shutdown delay in underway. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.59 |
| upsAlarmInsufficientResources mandatory Insufficient resources alarm.
The load cannot by supplied by alternate source (A005) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.6 |
| upsAlarmShutdownRequestt mandatory The shutdown command has been sent to servers agent. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.60 |
| upsAlarmShutdownImminent mandatory The UPS will turn OFF,
according the standby schedule settings. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.61 |
| upsAlarmAwaitingPower mandatory The UPS output is in standby,
and the UPS is awaiting the return of input power. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.62 |
| upsAlarmRedundancyLost mandatory Redundancy lost alarm. (A006) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.7 |
| upsAlarmOutputShortCircuit mandatory An output short-circuit has been detected by UPS. (A007) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.8 |
| upsAlarmMaintenance mandatory The UPS requests a maintenance service check. (A012) | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.7.1.6.3.9 |