es1DcSys1CfgBatCurrentLimitationCurrentLimit

SITE-MONITORING-MIB · .1.3.6.1.4.1.12551.20.1.20.1.20.1.15.3.114

Object

scalar r/w SNMPv2-TCDisplayString
The max charging current can be computed using the installed capacity times the wished C rate. For the specific case of NiZn battery, the recommended standard charging current limitation is C/4 while fast charging is C/2.

Context

MIB
SITE-MONITORING-MIB
OID
.1.3.6.1.4.1.12551.20.1.20.1.20.1.15.3.114
Type
scalar
Access
readwrite
Status
current
Parent
es1DcSys1ConfigList
Siblings
63

Syntax

SNMPv2-TCDisplayString
Source
SNMPv2-TCDisplayString
Base type
OctetString

Values & Constraints

Type Constraints
range: 0..255

Related Objects

Sibling Objects