setOutletPowerupMode

SCHLEIFENBAUER-GENERIC-MIB · .1.3.6.1.4.1.44568.1.1.4.1.1.7

Object

column r/w Enumeration
Behaviour of outlets on power-up. 0 = off, 1 = same state as at power down use default switch delay, 2 = same state, but delayed by individual delay timer, 3 = Outlets will always stay on (even at power down!)

Context

MIB
SCHLEIFENBAUER-GENERIC-MIB
OID
.1.3.6.1.4.1.44568.1.1.4.1.1.7
Type
column
Access
readwrite
Status
current
Parent
deviceSettingsEntry
Table
deviceSettingsTable
Siblings
8

Syntax

Enumeration

Values & Constraints

Enumerated Values
0no-switching-on-powerup
1system-wide-outlet-delay
2system-wide-and-individual-outlet-delay
3no-switching-on-power-down