outletReactivePower
SCHLEIFENBAUER-GENERIC-MIB ·
.1.3.6.1.4.1.44568.1.1.8.1.1.8
Object
Reactive power (volt-amps reactive, in VAR) 100x, MEASURED by the device.
Context
- MIB
- SCHLEIFENBAUER-GENERIC-MIB
- OID
.1.3.6.1.4.1.44568.1.1.8.1.1.8- Type
- column
- Access
- readonly
- Status
- current
- Units
- 0.01VAR
- Parent
- deviceOutletsEntry
- Table
- deviceOutletsTable
- Siblings
- 22
Syntax
0.01VAR SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| outletDeviceIndex A unique value for each PDU. Its value
ranges between 1 and the value of pduCount. | column | Integer32 | .1.3.6.1.4.1.44568.1.1.8.1.1.1 |
| outletActualCurrent Actual apparent 100x, RMS current per outlet. | column | 0.01A SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.10 |
| outletActualVoltage Actual voltage on outlet 100x. | column | 0.01V SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.11 |
| outletType Outlet types: 0: Unknown, 1: BS, 2: C13, 3: C13 IEC Lock, 4: C19, 5: C19 IEC Lock, 6: CEE 16A 1 phase, 7: CEE 16A 3 phase, 8: CEE 32A 1 phase, 9: CEE 32A 3 phase, 10: CEE 63A 1 ph… | column | 1 Enumeration | .1.3.6.1.4.1.44568.1.1.8.1.1.12 |
| outletPhase A mapping to which input each outlet is connected to. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.13 |
| outletCurrentState The state of the outlet relay(s). | column | Enumeration | .1.3.6.1.4.1.44568.1.1.8.1.1.14 |
| outletApparentEnergy The apparent accumulated energy VAh of each outlet 100x. | column | 5645VAh SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.15 |
| outletCrestFactor The crest factor per outlet 100x. the ratio of peak values to the effective value. | column | 0.01% SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.16 |
| outletPeakCurrent Peak apparent 100x, RMS current of an outlet; highest value since last reset of the peaks. | column | 0.01A SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.17 |
| outletMaxRatedAmps Outlet maximum rated current in A. | column | 1A SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.18 |
| outletThd Total harmonic distortion per outlet 100x. | column | 0.01% SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.19 |
| outletIndex An outlet index in pdu. | column | Integer32 | .1.3.6.1.4.1.44568.1.1.8.1.1.2 |
| outletPowerCycle Writing '1' will cause the outlet to power cycle. | column | 1 SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.20 |
| outletPowerCycleDelay Outlet individual power cycle timer. This is the amount, in seconds. | column | 1 SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.21 |
| outletSwitchDelay Delay before an individual outlet's relay switches on at power-up, in seconds. | column | 1 SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.22 |
| outletBranch A mapping to which branch each outlet is connected to. | column | 1 SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.23 |
| outletName User configurable naming of individual outlets. | column | OctetString | .1.3.6.1.4.1.44568.1.1.8.1.1.3 |
| outletEnergyTotal Total kWh of selected outlet. This value is not resetable. | column | KWh SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.4 |
| outletEnergySubtotal kWh subtotal register of selected output. | column | KWh SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.5 |
| outletActivePower Output power (in W), MEASURED by the device x100 using current, voltage, and power factor measurements of an outlet. | column | 0.01W SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.6 |
| outletApparentPower Output VA (volt-amps, in VA) 100x, MEASURED by the device using current and voltage measurements of an outlet. | column | 0.01VA SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.7 |
| outletPowerFactor Power factor x100 per outlet. | column | 0.01% SNMPv2-SMIInteger32 | .1.3.6.1.4.1.44568.1.1.8.1.1.9 |