sdbDevStPowerSaverMode
SCHLEIFENBAUER-DATABUS-MIB ·
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.6
Object
column
r/w
s Integer32
Set backlight on time in seconds. 0 keeps display always on. Note that keeping the backlight on may decrease luminosity over time.
Context
- MIB
- SCHLEIFENBAUER-DATABUS-MIB
- OID
.1.3.6.1.4.1.31034.12.1.1.2.5.1.1.6- Type
- column
- Access
- readwrite
- Status
- current
- Units
- s
- Parent
- sdbDevStEntry
- Table
- sdbDevStTable
- Siblings
- 12
Syntax
s Integer32
Values & Constraints
Object Constraints
range: 0-0
range: 10-10
range: 60-60
range: 120-120
range: 240-240
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| sdbDevStLocalAlertReset Allow alerts to be reset locally on device by pushing one of the
buttons. | column | Enumeration | .1.3.6.1.4.1.31034.12.1.1.2.5.1.1.10 |
| sdbDevStCurrentDropDetection Enables the current drop detection function. | column | Enumeration | .1.3.6.1.4.1.31034.12.1.1.2.5.1.1.11 |
| sdbDevStUsbMode Allow the USB port to be used for specific tasks | column | Enumeration | .1.3.6.1.4.1.31034.12.1.1.2.5.1.1.13 |
| sdbDevStSensorChangeAlertMode Enable sensoe change alerts | column | Enumeration | .1.3.6.1.4.1.31034.12.1.1.2.5.1.1.14 |
| sdbDevStOutletUnlockOverride Overrides the timeout. If this is set to 1 then the timeout will be ignored, otherwise the timeout will be taken into account. | column | Enumeration | .1.3.6.1.4.1.31034.12.1.1.2.5.1.1.15 |
| sdbDevStAutoResetAlerts Auto reset alerts configuration.
If set to 0 the auto reset alerts feature is disabled. If set to a
value greater then 0, the auto reset alerts feature is enabled and
alerts will … | column | seconds Integer32 | .1.3.6.1.4.1.31034.12.1.1.2.5.1.1.2 |
| sdbDevStExtendedNames Use original or longer names for inputs, outlets and sensors. | column | Enumeration | .1.3.6.1.4.1.31034.12.1.1.2.5.1.1.3 |
| sdbDevStPeakDuration Amount of ms a current peak should last before an alert is raised. | column | ms Integer32 | .1.3.6.1.4.1.31034.12.1.1.2.5.1.1.4 |
| sdbDevStFixedOutletDelay Minimal delay between two successive relay switches in milliseconds.
Minimal delay is 100 ms. Will always be respected! | column | ms Integer32 | .1.3.6.1.4.1.31034.12.1.1.2.5.1.1.5 |
| sdbDevStOutletPowerUpMode Behaviour of outlets on power-up. | column | Enumeration | .1.3.6.1.4.1.31034.12.1.1.2.5.1.1.7 |
| sdbDevStMaximumTemperature Maximum temperature threshold
An alert will be generated whenever the temperature is above this
value. Zero means disabled. | column | degrees Celsius Integer32 | .1.3.6.1.4.1.31034.12.1.1.2.5.1.1.8 |
| sdbDevStDisplayOrientation Display orientation. | column | Enumeration | .1.3.6.1.4.1.31034.12.1.1.2.5.1.1.9 |