startEqualize
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.70.30.100
Object
scalar
r/w
NoData
This command attempts to start the Equalize process.
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.70.30.100- Type
- scalar
- Access
- readwrite
- Status
- current
- Parent
- equalize
- Siblings
- 12
Syntax
NoData
- Source
- NoData
- Base type
OctetString
Values & Constraints
Type Constraints
range: 0
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| equalizeState Indicates the state of the Equalize process: Disabled, Inactive or Active. | scalar | ControlProcessState | .1.3.6.1.4.1.1918.2.14.10.70.30.10 |
| stopEqualize This command stops the Equalize process if it is currently active. | scalar | NoData | .1.3.6.1.4.1.1918.2.14.10.70.30.110 |
| equalizeVoltage The bus voltage maintained during an Equalize cycle. The bus voltage is further adjusted by Temperature Compensation. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.30.12 |
| equalizeSmartAlarm The smart alarm that will attempt to start and stop Equalize. To disable set to 0. The recognition period does not apply to start equalize. | scalar | Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.70.30.120 |
| equalizeOffsetVoltage The adjustment to the bus voltage being applied due to the Equalize process. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.30.13 |
| periodicEqualizeFirstDateTime The date and time that the first scheduled Equalize will occur. Subsequent Equalize cycles will occur at every Equalize Interval thereafter. | scalar | JulianDateUtc25 | .1.3.6.1.4.1.1918.2.14.10.70.30.15 |
| equalizeInterval The time between scheduled Equalize cycles. The interval period begins at the start of an Equalize. Zero disables scheduled Equalizes. | scalar | d TimeIntervalInDays | .1.3.6.1.4.1.1918.2.14.10.70.30.17 |
| nextEqualizeStartTime The start time of the next scheduled Equalize cycle. The value is NaN if Equalize is active or Periodic Equalize function is disabled. | scalar | JulianDateUtc25 | .1.3.6.1.4.1.1918.2.14.10.70.30.20 |
| equalizeDuration The duration of a scheduled Equalize. | scalar | min TimeIntervalInMinutes | .1.3.6.1.4.1.1918.2.14.10.70.30.30 |
| equalizeRemainingTime The time until the current Equalize cycle will stop. The value is NaN if the Equalize is inactive. | scalar | s TimeIntervalInSeconds | .1.3.6.1.4.1.1918.2.14.10.70.30.40 |
| enableEqualize Applies a controlled overcharge to the battery by raising the charge voltage for a set time. This may be required to ensure all cells are fully charged, remove sulphation, or redi… | scalar | EnableState | .1.3.6.1.4.1.1918.2.14.10.70.30.5 |
| equalizeStartAllowed Indicates if an Equalize cycle is allowed to start or the reason why not. An Equalize cycle cannot start if there are no rectifiers with AC power. | scalar | CanStart | .1.3.6.1.4.1.1918.2.14.10.70.30.9 |