redundancy
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.60.70.50
Object
scalar
r/w
Redundancy
For N+1 there is always one spare rectifier above what is needed. N+2 maintains 2 spare. For N there are always at least enough rectifiers to supply the load. If an alternative energy source is supplying the load, all rectifiers can be shut down. Rectifiers will restart when the battery begins to discharge.
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.60.70.50- Type
- scalar
- Access
- readwrite
- Status
- current
- Parent
- loadBasedRectifierShutdownConfig
- Siblings
- 4
Syntax
Redundancy
- Source
- Redundancy
- Base type
Enumeration
Values & Constraints
Type Values
1 | n |
2 | nPlus1 |
3 | nPlus2 |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| resetRunTimes This command attempts to reset the Run Time on each individual rectifier. | scalar | NoData | .1.3.6.1.4.1.1918.2.14.10.60.70.100 |
| rectCycleLowThreshold Rectifiers will only be shut down by the LBRS process if the load power is below this percentage of total system power. | scalar | % Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.60.70.20 |
| rectCycleHighThreshold Additional rectifiers will be started by the LBRS process if the load power is above this percentage of total system power. | scalar | % Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.60.70.30 |
| rectCycleInterval The time interval in minutes that rectifiers are cycled when the LBRS process is active. | scalar | min TimeIntervalInMinutes | .1.3.6.1.4.1.1918.2.14.10.60.70.40 |