rectCycleHighThreshold
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.60.70.30
Object
scalar
r/w
% Unsigned8
Additional rectifiers will be started by the LBRS process if the load power is above this percentage of total system power.
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.60.70.30- Type
- scalar
- Access
- readwrite
- Status
- current
- Units
- %
- Parent
- loadBasedRectifierShutdownConfig
- Siblings
- 4
Syntax
% Unsigned8
- Source
- Unsigned8
- Base type
Integer32
Values & Constraints
Type Constraints
range: 0..255
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| resetRunTimes This command attempts to reset the Run Time on each individual rectifier. | scalar | NoData | .1.3.6.1.4.1.1918.2.14.10.60.70.100 |
| rectCycleLowThreshold Rectifiers will only be shut down by the LBRS process if the load power is below this percentage of total system power. | scalar | % Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.60.70.20 |
| rectCycleInterval The time interval in minutes that rectifiers are cycled when the LBRS process is active. | scalar | min TimeIntervalInMinutes | .1.3.6.1.4.1.1918.2.14.10.60.70.40 |
| redundancy For N+1 there is always one spare rectifier above what is needed. N+2 maintains 2 spare. For N there are always at least enough rectifiers to supply the load. If an alternative en… | scalar | Redundancy | .1.3.6.1.4.1.1918.2.14.10.60.70.50 |