peakLoadReductionState
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.70.85.10
Object
scalar
PeakLoadReductionState
The state of Peak Load Reduction.
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.70.85.10- Type
- scalar
- Access
- readonly
- Status
- current
- Parent
- peakLoadReduction
- Siblings
- 8
Syntax
PeakLoadReductionState
- Source
- PeakLoadReductionState
- Base type
Enumeration
Values & Constraints
Type Values
0 | disabled |
1 | inactiveNotRunning |
2 | inactiveNoBusVoltage |
3 | inactiveNotEnoughRectifiers |
4 | inactiveExceededMaxDuration |
5 | heldAtMinimumBusVoltage |
6 | activeCharge |
7 | activeDischarge |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| enablePeakLoadReduction If Enabled, the Peak Load Reduction will force the battery to take the load when required. | scalar | EnableState | .1.3.6.1.4.1.1918.2.14.10.70.85.20 |
| peakLoadReductionRunningTime The time that Peak Load Reduction has been running. | scalar | s TimeIntervalInSeconds | .1.3.6.1.4.1.1918.2.14.10.70.85.30 |
| peakLoadReductionOffsetVoltage The adjustment to the bus voltage being applied due to Peak Load Reduction. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.85.40 |
| peakLoadReductionSmartAlarm The smart alarm that will start Peak Load Reduction. To disable set to 0. | scalar | Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.70.85.50 |
| peakLoadReductionMaxDuration The maximum time that Peak Load Reduction can be active. | scalar | min TimeIntervalInMinutes | .1.3.6.1.4.1.1918.2.14.10.70.85.60 |
| peakLoadReductionLowVoltageLimit The lowest bus voltage that Peak Load Reduction can discharge the battery to. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.85.70 |
| peakLoadReductionScheduledStartTime This will start Peak-Load-Reduction for Peak-Load-Reduction-Scheduled-Duration, if activating smart alarm is not active. | scalar | JulianDateUtc25 | .1.3.6.1.4.1.1918.2.14.10.70.85.80 |
| peakLoadReductionScheduledDuration This will end Peak-Load-Reduction this time after Peak-Load-Reduction-Scheduled-Start-Time, if activating smart alarm is not active. A zero will disable Peak-Load-Reduction if act… | scalar | min TimeIntervalInMinutes | .1.3.6.1.4.1.1918.2.14.10.70.85.90 |