floatVoltage

RPS-SC300-MIB · .1.3.6.1.4.1.1918.2.14.10.70.10.10

Object

scalar r/w 0.01 V Float
The voltage required to maintain optimum battery charge (at the nominal ambient temperature). Use the value recommended by the battery manufacturer. The bus voltage may be adjusted above or below this value by Temperature Compensation, Fast Charge, Battery Test, Equalize or Battery Current Limit.

Context

MIB
RPS-SC300-MIB
OID
.1.3.6.1.4.1.1918.2.14.10.70.10.10
Type
scalar
Access
readwrite
Status
current
Units
0.01 V
Parent
voltageControl
Siblings
11

Syntax

0.01 V Float
Source
Float
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647

Related Objects

Sibling Objects