fastCharge
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.70.40
Object
node
No description available.
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.70.40- Type
- node
- Status
- current
- Parent
- controlFunctions
- Siblings
- 13
- Children
- 13
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| voltageControl | node | - | .1.3.6.1.4.1.1918.2.14.10.70.10 |
| temperatureCompensation | node | - | .1.3.6.1.4.1.1918.2.14.10.70.20 |
| resetAhDischarged This command resets controller battery state information (Amp hours discharged) and reverts all control process states to Inactive. | scalar | NoData | .1.3.6.1.4.1.1918.2.14.10.70.25 |
| ahDischargedFloatResetRate Once the battery has returned to float the Ah discharged figure is adjust towards zero by this factor multiplied by Battery-State-Threshold. In Solar applications where the amount… | scalar | 0.1 Float | .1.3.6.1.4.1.1918.2.14.10.70.27 |
| equalize | node | - | .1.3.6.1.4.1.1918.2.14.10.70.30 |
| controlState Indicates the state of control process, e.g. Equalize, Fast Charge or Normal. | scalar | ControlState | .1.3.6.1.4.1.1918.2.14.10.70.5 |
| batteryCurrentLimit | node | - | .1.3.6.1.4.1.1918.2.14.10.70.50 |
| batteryTest | node | - | .1.3.6.1.4.1.1918.2.14.10.70.70 |
| lvd | node | - | .1.3.6.1.4.1.1918.2.14.10.70.75 |
| generatorControl | node | - | .1.3.6.1.4.1.1918.2.14.10.70.80 |
| peakLoadReduction | node | - | .1.3.6.1.4.1.1918.2.14.10.70.85 |
| energyMeters | node | - | .1.3.6.1.4.1.1918.2.14.10.70.87 |
| fanController | node | - | .1.3.6.1.4.1.1918.2.14.10.70.88 |
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| fastChargeState Indicates the state of Fast Charge process: Disabled, Inactive, Active or Pending. | scalar | ControlProcessState | .1.3.6.1.4.1.1918.2.14.10.70.40.10 |
| stopFastCharge This command stops the Fast Charge process if it is currently active. | scalar | NoData | .1.3.6.1.4.1.1918.2.14.10.70.40.100 |
| fastChargeStartAllowed Indicates if a Fast Charge is allowed to start or the reason why not. Fast Charge cannot start if there are no rectifiers with AC power, or the battery is not discharged. | scalar | CanStart | .1.3.6.1.4.1.1918.2.14.10.70.40.12 |
| fastChargeVoltage The bus voltage maintained during Fast Charge (use the value recommended by the battery manufacturer). Adjustments for Temperature Compensation and Battery Current Limit also appl… | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.40.15 |
| fastChargeOffsetVoltage The adjustment to the bus voltage being applied due to the Fast Charge. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.40.17 |
| fastChargeAhDischarged The current level of battery discharge. | scalar | Ah Float | .1.3.6.1.4.1.1918.2.14.10.70.40.20 |
| fastChargeMaximumDuration The maximum duration of a Fast Charge (use the value recommended by the battery manufacturer). | scalar | min TimeIntervalInMinutes | .1.3.6.1.4.1.1918.2.14.10.70.40.30 |
| fastChargeAmpereHourThreshold If the battery has been discharged until the charge level is this value below full charge, then Fast Charge occurs when AC power is restored. The threshold is given as a percentag… | scalar | % Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.70.40.35 |
| fastChargeVoltageThreshold If the bus voltage drops below this value then Fast Charge occurs when AC power is restored. Fast charge can also be triggered based on the Fast Charge Ampere Hour Threshold. | scalar | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.40.40 |
| fastChargeRechargePercentage The ratio of recharge ampere-hours required to restore the battery to fully charged status to the ampere-hours discharged. | scalar | % Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.70.40.45 |
| fastChargeAmpereHourStopThreshold Fast charge will only run until the battery has been recharged to a charge percentage of this value below full charge. This mostly useful when fast charge is used to control a gen… | scalar | % Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.70.40.47 |
| enableFastCharge After an AC power outage, Fast Charge automatically increases the float voltage of the DC power system to recharge the batteries as quickly as possible. Enable Fast Charge if the … | scalar | EnableState | .1.3.6.1.4.1.1918.2.14.10.70.40.5 |
| fastChargeMaximumTimeRemaining This timer is started when a Fast Charge cycle starts and runs while Fast Charge remains active. It is suspended and resumed when Fast Charge is suspended and resumed respectively… | scalar | s TimeIntervalInSeconds | .1.3.6.1.4.1.1918.2.14.10.70.40.50 |