btrStateOfHealth
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.100.44
Object
scalar
% Percentile8Nan
The health of the battery measured as the estimated C10 capacity at the end of the last discharge as a percentage of the configured capacity. The accuracy of this value depends on the depth of the last discharge and it is only updated if the battery is discharged by at least 25% of its estimated capacity.
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.100.44- Type
- scalar
- Access
- readonly
- Status
- current
- Units
- %
- Parent
- battery
- Siblings
- 14
Syntax
% Percentile8Nan
- Source
- Percentile8Nan
- Base type
Enumeration
Values & Constraints
Type Values
255 | notAvailable |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| batteryCapacity The rated 10-hour (C10) capacity of the battery. 0 = no battery is installed. | scalar | Ah SNMPv2-SMIInteger32 | .1.3.6.1.4.1.1918.2.14.10.100.10 |
| cellsPerString The number of 2V battery cells per string. Zero means no battery is installed. | scalar | Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.100.20 |
| batteryTemperature The average of all analog inputs configured as battery temperature inputs. | scalar | °C Float | .1.3.6.1.4.1.1918.2.14.10.100.30 |
| batteryCurrent The total current flowing to/from the batteries. If positive, the battery is being charged. This value may be measured by the battery current shunt(s) if present or calculated fro… | scalar | A Float | .1.3.6.1.4.1.1918.2.14.10.100.40 |
| batteryType The name or type of the battery. | scalar | OctetString | .1.3.6.1.4.1.1918.2.14.10.100.42 |
| btrTimeRemaining An estimate of the time remaining until the average cell discharge voltage reaches the configured end voltage. This value is only available during a discharge if the battery has b… | scalar | min TimeIntervalInMinutes | .1.3.6.1.4.1.1918.2.14.10.100.43 |
| batteryChargeState Indicates the current state of the battery. | scalar | BatteryChargeState | .1.3.6.1.4.1.1918.2.14.10.100.45 |
| batteryStateThreshold The threshold used to determine the battery state. If the battery current is greater than the value, the battery state is Charge. If the battery current is less than the negative … | scalar | 0.1 A Float | .1.3.6.1.4.1.1918.2.14.10.100.47 |
| endOfChargeAction To ensure that there is no residual AhD error at the end of the charge, AhD can be set to zero after each charge. For new installations, Set Ah Discharged to zero after Equalize a… | scalar | EndOfChargeAction | .1.3.6.1.4.1.1918.2.14.10.100.48 |
| batteryDesign | node | - | .1.3.6.1.4.1.1918.2.14.10.100.49 |
| midPointMonitoring | node | - | .1.3.6.1.4.1.1918.2.14.10.100.50 |
| batteryTimeRemaining | node | - | .1.3.6.1.4.1.1918.2.14.10.100.60 |
| batteryCharacterizationDataTable Table for batteryCharacterizationData | table | - | .1.3.6.1.4.1.1918.2.14.10.100.62 |