The current operating mode of the transfer switch. When the ATS is in automatic mode, generator starting and ATS transferring is all done automatically as needed based on the state of source 1. Automatic operation is halted when the ATS is in either of the notInAuto modes. A mode of notInAuto indicates that the automatic operation switch is in the disabled position, as indicated by the xATSSwitchStatusAutomaticOperationSwitch OID. The notInAutoAbnormal condition indicates that an abnormal condition has caused the transfer switch to halt automatic operation. In this case, traps can indicate the exact problem. In the case of notInAutoAbnormal, refer to the operation manual for details on how debug the condition and restore automatic operation.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.17.3.1.2- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- xATSSwitchStatus
- Siblings
- 3
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | automatic |
2 | notInAutoAbnormal |
3 | notInAuto |
4 | unknown |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| xATSSwitchStatusSelectedSource mandatory The source which is currently selected, i.e. supplying power to the load. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.17.3.1.1 |
| xATSSwitchStatusAutomaticOperationSwitch mandatory The position of the automatic operation switch on the front of the transfer switch. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.17.3.1.3 |
| xATSSwitchStatusEngineStartSignal mandatory The position of the Start/Stop contact which signals the generator
engine to start/run. When the ATS is in automatic mode,