xATSSwitchStatusEngineStartSignal
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.17.3.1.4
Object
scalar
mandatory
Enumeration
The position of the Start/Stop contact which signals the generator engine to start/run. When the ATS is in automatic mode, generator starting/stopping is under ATS control.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.17.3.1.4- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- xATSSwitchStatus
- Siblings
- 3
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | run |
2 | stop |
3 | unknown |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| xATSSwitchStatusSelectedSource mandatory The source which is currently selected, i.e. supplying power to the load. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.17.3.1.1 |
| xATSSwitchStatusOperationalMode mandatory The current operating mode of the transfer switch. When the ATS is in
automatic mode, generator starting and ATS transferring is all done automatically
as needed based on the stat… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.17.3.1.2 |
| xATSSwitchStatusAutomaticOperationSwitch mandatory The position of the automatic operation switch on the front of the transfer switch. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.17.3.1.3 |