xATSSwitchSettingsMinPhaseBalance

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.17.3.2.4

Object

scalar mandatory r/w Integer32
The minimum required phase balance at source 1.
When the percentage difference between the minimum and maximum
phase voltage measurements at source 1 is greater than this value,
source quality is considered bad and the generator run signal
is asserted to begin generator operation.
Specified as a percentage. A value of zero indicates that phase balance
is ignored when determining source quality. -1 if not available.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.17.3.2.4
Type
scalar
Access
readwrite
Status
mandatory
Parent
xATSSwitchSettings
Siblings
9

Syntax

Integer32
Source
COPS-PR-SPPIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647