xATSSwitchSettingsMaxFrequencyDeviation
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.17.3.2.3
Object
scalar
mandatory
r/w
Integer32
The maximum acceptable frequency deviation condition from nominal at source 1. When source 1 frequency is outside the specified range, source quality is considered bad and the generator run signal is asserted to begin generator operation. Specified in tenths of Hertz above or below nominal. A value of zero indicates that frequency is ignored when determining source quality. -1 if not available.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.17.3.2.3- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- xATSSwitchSettings
- Siblings
- 9
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| xATSSwitchSettingsLowVoltageTransferPoint mandatory The lowest acceptable voltage condition at source 1.
When any phase of source 1 is lower than this voltage,
source quality is considered bad and the generator run signal
is assert… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.17.3.2.1 |
| xATSSwitchSettingsSetToFactoryDefaults mandatory Sets all transfer switch settings to factory default values. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.17.3.2.10 |
| xATSSwitchSettingsHighVoltageTransferPoint mandatory The highest acceptable voltage condition at source 1.
When any phase of source 1 is greater than this voltage,
source quality is considered bad and the generator run signal
is ass… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.17.3.2.2 |
| xATSSwitchSettingsMinPhaseBalance mandatory The minimum required phase balance at source 1.
When the percentage difference between the minimum and maximum
phase voltage measurements at source 1 is greater than this value,
s… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.17.3.2.4 |
| xATSSwitchSettingsNominalRotation mandatory The nominal phase rotation (or phase sequence) required by the load.
For certain types of equipment, such as rotating machinery, phase rotation
is critical for proper operation as… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.17.3.2.5 |
| xATSSwitchSettingsAllowClosedTransfer mandatory This setting enables seamless (closed) transfers between sources.
When possible, both source 1 and source 2 are closed to the output
for a brief time. If closed transfer is not po… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.17.3.2.6 |
| xATSSwitchSettingsMaxSyncTime mandatory When attempting/seeking to perform a closed transfer, this setting defines
the maximum time allowed before the transfer switch will give up and perform
an open transfer. Specified… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.17.3.2.7 |
| xATSSwitchSettingsNeutralTransferTime mandatory This setting defines how long both source 1 and source 2 will be
disconnected from the output, during an open transfer.
Specified in seconds.
-1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.17.3.2.8 |
| xATSSwitchSettingsClearLatchedAlarms mandatory Clears any latched alarm conditions. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.17.3.2.9 |