xATSSwitchSettingsHighVoltageTransferPoint

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.17.3.2.2

Object

scalar mandatory r/w Integer32
The highest acceptable voltage condition at source 1.
When any phase of source 1 is greater than this voltage,
source quality is considered bad and the generator run signal
is asserted to begin generator operation.
Specified in volts,  line-to-line for a 3-wire service or
line-to-neutral for a 4-wire service.
-1 if not available.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.17.3.2.2
Type
scalar
Access
readwrite
Status
mandatory
Parent
xATSSwitchSettings
Siblings
9

Syntax

Integer32
Source
COPS-PR-SPPIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647