xATSGeneratorSettingsCrankRestTime
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.18.1.5.7
Object
scalar
mandatory
Integer32
The pause duration, in seconds, following an unsuccessful attempt to start the generator. Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled. -1 if not available.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.18.1.5.7- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- xATSGeneratorSettings
- Siblings
- 8
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| xATSGeneratorSettingsVoltageAdjust mandatory The voltage adjust of the generator.
Specified in volts line-to-line,
or -1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.5.1 |
| xATSGeneratorSettingsFrequencyAdjust mandatory The frequency adjust of the generator.
Specified in tenths of Hertz. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.5.2 |
| xATSGeneratorSettingsStartDelay mandatory The delay, in seconds, after the remote run signal is activated
before the generator's engine will be cranked to start,
or -1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.5.3 |
| xATSGeneratorSettingsStopDelay mandatory The delay, in seconds, before the generator will stop
after the remote run signal is deactivated,
or -1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.5.4 |
| xATSGeneratorSettingsCrankCycleEnable mandatory When Crank Cycle is enabled, the engine will be cranked up to the time
specified by the xATSGeneratorSettingsCrankTime OID.
If the generator's engine does not start, there will be… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.18.1.5.5 |
| xATSGeneratorSettingsCrankTime mandatory The duration of engine cranking, in seconds, when starting the generator.
Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled.
-1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.5.6 |
| xATSGeneratorSettingsNumberCrank mandatory The number of failed crank attempts before giving up on starting the generator.
Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled.
-1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.5.8 |
| xATSGeneratorSettingsMetricUnit mandatory Specifies the use of metric units in generator related OIDs, as well
as on all other interfaces including the generator's local interface. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.18.1.5.9 |