xATSGeneratorServiceCalendarIntervalThreshold
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.18.1.6.12
Object
scalar
mandatory
r/w
Enumeration
Calendar-based service interval. When the next service date, as indicated by the xATSGeneratorServiceNextServiceDate OID is in the past, generator is due for service.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.18.1.6.12- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- xATSGeneratorService
- Siblings
- 11
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | disabled |
2 | interval1month |
3 | interval2month |
4 | interval3month |
5 | interval6month |
6 | intervalyearly |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| xATSGeneratorServiceTotalRunHoursLifetime mandatory Total time that the generator engine has been run,
over the life of the generator. Measured in hours.
-1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.6.1 |
| xATSGeneratorServiceRunHoursUntilServiceDate mandatory Run hours until the next generator service is due, in hours.
Based on the xATSGeneratorServiceRunHoursThreshold OID
or -1 if the run hour-based threshold is set to off. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.6.10 |
| xATSGeneratorServiceRunHoursThreshold mandatory Run hour-based service interval. When the run-hours since
service surpasses this threshold, generator service is due. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.18.1.6.11 |
| xATSGeneratorServiceEngineStartsLifetime mandatory Number of engine starts over the life of the generator.
-1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.6.2 |
| xATSGeneratorServiceTotalkWhLifetime mandatory Total kWh of operation over the life of the generator.
-1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.6.3 |
| xATSGeneratorServiceTotalRunHoursSinceMaintenance mandatory Total time that the generator engine has been run,
since last service maintenance. Measured in tenths of hours.
-1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.6.4 |
| xATSGeneratorServiceEngineStartsSinceMaintenance mandatory Number of engine starts since last service maintenance.
-1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.6.5 |
| xATSGeneratorServiceTotalkWhMaintenance mandatory Total kWh of operation since last service maintenance.
-1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.6.6 |
| xATSGeneratorServiceResetRecord mandatory Resets the engine start counter, engine run-hours, and kWh values that have
accumulated in the generator since last maintenance.
Also, the last service date will be reset to the c… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.18.1.6.7 |
| xATSGeneratorServiceRecordResetDate mandatory Date at which the generator's service record was reset, in dd-mmm-yyyy format. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.18.1.6.8 |
| xATSGeneratorServiceNextServiceDate mandatory Date at which the next generator service is due in dd-mmm-yyyy format.
Based on the xATSGeneratorServiceCalendarIntervalThreshold OID
or '' if the calendar-based threshold is set … | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.18.1.6.9 |