xATSGeneratorFuelSystemEstimatedRunTime
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.18.1.7.5
Object
scalar
mandatory
Integer32
An estimate of available runtime for the generator, based on available fuel as specified in the xATSGeneratorFuelSystemFuelLevel OID and kW load as specified in the xATSGeneratorFuelSystemRuntimePower OID. Measured in tenths of hours, or -1 if not available.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.18.1.7.5- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- xATSGeneratorFuelSystem
- Siblings
- 8
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| xATSGeneratorFuelSystemType mandatory The type of fuel used by the generator. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.18.1.7.1 |
| xATSGeneratorFuelSystemTankSize mandatory Size of the generator's fuel tank.
Specified in gallons or liters, based on the value of the
xATSGeneratorSettingsMetricUnit OID, or -1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.7.2 |
| xATSGeneratorFuelSystemFuelLevel mandatory Fuel remaining in the generator tank.
Measured in percent of tank fill, or -1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.7.3 |
| xATSGeneratorFuelSystemRuntimePower mandatory The power value used in the runtime remaining calculation.
Measured in tenths of kW, or -1 if not available. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.7.4 |
| xATSGeneratorFuelSystemLowRunTimeThreshold mandatory Threshold below which a low runtime alarm will exist. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.18.1.7.6 |
| xATSGeneratorFuelSystemVeryLowRunTimeThreshold mandatory Threshold below which a very low runtime alarm will exist. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.18.1.7.7 |
| xATSGeneratorFuelSystemLowFuelLevelThreshold mandatory Threshold below which a low fuel alarm will exist, with a value of 0 indicating disabled.
Specified as percent of tank fill. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.7.8 |
| xATSGeneratorFuelSystemVeryLowFuelLevelThreshold mandatory Threshold below which a very low fuel alarm will exist, with a value of 0 indicating disabled.
Specified as percent of tank fill. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.18.1.7.9 |