upsHighPrecInputLineVoltage
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.3.3.1
Object
The current utility line voltage in tenths of VAC.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.3.3.1- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- upsHighPrecInput
- Siblings
- 8
Syntax
RFC1155-SMIGauge
- Source
- RFC1155-SMIGauge
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsHighPrecInputMaxLineVoltage mandatory The maximum utility line voltage in tenths of VAC over the
previous 1 minute period. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.318.1.1.1.3.3.2 |
| upsHighPrecInputMinLineVoltage mandatory The minimum utility line voltage in tenths of VAC over the
previous 1 minute period. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.318.1.1.1.3.3.3 |
| upsHighPrecInputFrequency mandatory The current input frequency to the UPS system in tenths of Hz. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.318.1.1.1.3.3.4 |
| upsHighPrecInputEnergyUsage mandatory The input energy usage of the UPS in hundredths of kWh. | scalar | Unsigned32 | .1.3.6.1.4.1.318.1.1.1.3.3.5 |
| upsHighPrecInputBypassVoltage mandatory The current bypass line voltage in tenths of VAC. | scalar | Unsigned32 | .1.3.6.1.4.1.318.1.1.1.3.3.6 |
| upsHighPrecInputBypassFrequency mandatory The current input bypass frequency to the UPS system in tenths of Hz. | scalar | Unsigned32 | .1.3.6.1.4.1.318.1.1.1.3.3.7 |
| upsHighPrecInputDCVoltage mandatory The DC input voltage, in tenths, of Volts on the inverter.
If not supported, return -1. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.3.3.8 |
| upsHighPrecInputDCCurrent mandatory The DC input current, in tenths of amperes, of the inverter. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.318.1.1.1.3.3.9 |