upsBasicBatteryStatus
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.2.1.1
Object
scalar
mandatory
Enumeration
The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime OID. A batteryInFaultCondition(4)value indicates that a battery installed has an internal error condition. noBatteryPresent(5) indicate that no battery is present (no battery, battery breaker open, etc)to perform the battery diagnostic test
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.2.1.1- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- upsBasicBattery
- Siblings
- 2
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | unknown |
2 | batteryNormal |
3 | batteryLow |
4 | batteryInFaultCondition |
5 | noBatteryPresent |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsBasicBatteryTimeOnBattery mandatory The elapsed time since the UPS has switched to battery
power. | scalar | RFC1155-SMITimeTicks | .1.3.6.1.4.1.318.1.1.1.2.1.2 |
| upsBasicBatteryLastReplaceDate mandatory The date when the UPS system's batteries were last replaced
in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value
is originally set in the factory. When the UPS batteri… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.2.1.3 |