upsBasicBatteryStatus

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.1.2.1.1

Object

scalar mandatory Enumeration
The status of the UPS batteries. A batteryLow(3) value
indicates the UPS will be unable to sustain the current
load, and its services will be lost if power is not restored.
The amount of run time in reserve at the time of low battery
can be configured by the upsAdvConfigLowBatteryRunTime OID.
A batteryInFaultCondition(4)value indicates that a battery
installed has an internal error condition.
noBatteryPresent(5) indicate that no battery is present (no battery, battery breaker open, etc)to perform the battery diagnostic test

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.1.2.1.1
Type
scalar
Access
readonly
Status
mandatory
Parent
upsBasicBattery
Siblings
2

Syntax

Enumeration

Values & Constraints

Enumerated Values
1unknown
2batteryNormal
3batteryLow
4batteryInFaultCondition
5noBatteryPresent

Related Objects