upsAdvStateLifeCycleManagement
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.11.2.14
Object
An ASCII string containing the 16 flags representing the life cycle management alerts
for the device. If the Network Card is unable to determine the values of the flags,
this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable,
it is set to 'NOT SUPPORTED'.
The flags are numbered from 1 to 16, and read from left
to right. The bits are defined as follows:
Flag 1: End of Warranty Soon
Flag 2: Battery Check Recommended
Flag 3: Service Period On Wearing Parts Expired
Flag 4: Secure Start-up Recommended
Flag 5: Fan Life Expired
Flag 6: DC Capacitor Life Expired
Flag 7: AC Capacitor Life Expired
Flag 8: Supply Service Life Expired
Flag 9: Ups Out Of Limits Warning
Flag 10: Air Filter Life Expired
Flag 11: <Not Used>
Flag 12: <Not Used>
Flag 13: <Not Used>
Flag 14: <Not Used>
Flag 15: <Not Used>
Flag 16: <Not Used>
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.11.2.14- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- upsAdvState
- Siblings
- 15
Syntax
RFC1213-MIBDisplayString
- Source
- RFC1213-MIBDisplayString
- Base type
OctetString
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAdvStateAbnormalConditions mandatory An ASCII string containing the 32 flags representing
the current active UPS faults. If the Network Card
is unable to determine the values of the flags, this
variable is set to 'UN… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.1 |
| upsAdvStateNumberoftimesonbattery mandatory Number of times the UPS was on battery.
Since the last reset of statistical data. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.11.2.10 |
| upsAdvStateNumberoftimesbypass mandatory Number of times the UPS was in bypass.
Since the last reset of statistical data. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.11.2.11 |
| upsAdvStateNumberoftimesNormal mandatory Number of times the UPS was in normal operation.
Since the last reset of statistical data. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.11.2.12 |
| upsAdvStateEcomode mandatory Eco mode status.
1: UPS is on Eco-mode
2: UPS is not on Eco-mode. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.11.2.13 |
| upsAdvStateGalaxyVseriesSpecificFault optional An ASCII string containing 32 flags representing
current active faults on a Galaxy V series UPS.
The upsAdvStateAbnormalConditions OID shall be used to report
active faults as per… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.15 |
| upsAdvStateGutorModularSpecificFaults optional An ASCII string containing the 64 flags representing
the current active Charger Rectifier and UPS specific faults for Gutor Modular models.
Flag allocation:
Flag 1 to 16 for break… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.16 |
| upsAdvStateSymmetra3PhaseSpecificFaults mandatory An ASCII string containing the 64 flags representing
the current active UPS specific faults for the Symmetra
3-Phase UPS models. If the Network Card is unable to
determine the val… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.2 |
| upsAdvStateDP300ESpecificFaults mandatory An ASCII string containing the 64 flags representing
the current active UPS specific faults for the Silcon
DP300E UPS models. If the Network Card is unable to
determine the values… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.3 |
| upsAdvStateSymmetraSpecificFaults mandatory An ASCII string containing the 64 flags representing
the current active UPS specific faults for the Symmetra
UPS models. If the Network Card is unable to determine
the values of t… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.4 |
| upsAdvStateSmartUPSSpecificFaults mandatory An ASCII string containing the 64 flags representing
the current active UPS specific faults for the Smart-UPS
UPS models. If the Network Card is unable to determine
the values of … | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.5 |
| upsAdvStateSystemMessages mandatory An ASCII string containing the 3 digit Decimal code
representing the current active message from the
System Message Register. Each code should remain active
for a minimum of 15 se… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.6 |
| upsAdvStateTotaltimeonbattery mandatory Total time the UPS has been in battery operation. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.7 |
| upsAdvStateTotaltimeonbypass mandatory Total time the UPS has been in bypass operation. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.8 |
| upsAdvStateTotaltimeonNormal mandatory Total time the UPS has been in normal operation. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.9 |