upsAdvStateGutorModularSpecificFaults
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.11.2.16
Object
An ASCII string containing the 64 flags representing
the current active Charger Rectifier and UPS specific faults for Gutor Modular models.
Flag allocation:
Flag 1 to 16 for breakers status (Charger Rectifier + UPS). 16 Flags
Flag 17 to 32 for module errors. 16 Flags
Flag 33 to 44 For charger errors. 12 Flags
Flag 45 to 54 for battery errors. 10 flags
Flag 55 to 64 for temperature errors. 10 flags
If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'.
If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'.
The flags are numbered from 1 to 64 and read from left to right. The bits are defined as follows:
Breaker (16 signals)
Flag 1: Rectifier AC mains breaker 1 is OPEN
Flag 2: Battery breaker 1 is OPEN
Flag 3: Rectifier DC output breaker is OPEN
Flag 4: PSU redundancy lost
Flag 5: DC distribution feeder is OPEN
Flag 6: Surge protection device is OPEN
Flag 7: Option input 1 is ACTIVE
Flag 8: Emergency power OFF is ACTIVE
Flag 9: Inverter DC input breaker is OPEN
Flag 10: Bypass AC mains breaker is OPEN
Flag 11: System AC output breaker is OPEN
Flag 12: AC distribution feeder is OPEN
Flag 13: Rectifier AC mains breaker 2 is OPEN
Flag 14: Battery breaker 2 is OPEN
Flag 15: <Not Used>
Flag 16: Roof fan disturbance is ACTIVE
Flag 1 to Flag 16 should be accessible for device type charger, inverter and UPS
Charger modules (16 signals)
Flag 17: < 1431 - Module configuration mismatch >
Flag 18: < 1433 - Load sharing error (All power modules) >
Flag 19: < 1435 - Fan fault (All power modules) >
Flag 20: < 1437 - Output voltage out of range (All power modules) >
Flag 21: < 1436 - Input voltage out of range (All power modules) >
Flag 22: < 1504 - System switched off >
Flag 23: < 1513 - Warning address reserve >
Flag 24: < 1514 - Address reserve error >
Flag 25: < 1515 - Power reserve error >
Flag 26: <Not Used>
Flag 27: <Not Used>
Flag 28: <Not Used>
Flag 29: <Not Used>
Flag 30: <Not Used>
Flag 31: <Not Used>
Flag 32: <Not Used>
ALL (12 signals)
Flag 33: < 6 - Common Alarm >
Flag 34: < 7 - Urgent incident >
Flag 35: < 8 - Non-urgent alarm >
Flag 36: < 9 - HMI-MCU Com. Error >
Flag 37: < 1428 - Equalization charge blocked >
Flag 38: < 1432 - Boost charge blocked >
Flag 39: < 1440 - High DC warning >
Flag 40: < 1441 - High DC shutdown >
Flag 41: < 1442 - Low DC warning >
Flag 42: < 1443 - Low DC shutdown >
Flag 43: <Not Used>
Flag 44: <Not Used>
Battery (10 signals)
Flag 45: < 11 - Battery symmetry fault >
Flag 46: < 1429 - Battery current limitation active >
Flag 47: < 1430 - Battery current limitation configuration error >
Flag 48: < 1512 - Battery temperature sensor defective >
Flag 49: <Not Used>
Flag 50: <Not Used>
Flag 51: <Not Used>
Flag 52: <Not Used>
Flag 53: <Not Used>
Flag 54: <Not Used>
Temperature (10 signals)
Flag 55: < 1444 - MCU temperature too high >
Flag 56: <Not Used>
Flag 57: <Not Used>
Flag 58: <Not Used>
Flag 59: <Not Used>
Flag 60: <Not Used>
Flag 61: <Not Used>
Flag 62: <Not Used>
Flag 63: <Not Used>
Flag 64: <Not Used>
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.11.2.16- Type
- scalar
- Access
- readonly
- Status
- optional
- Parent
- upsAdvState
- Siblings
- 15
Syntax
RFC1213-MIBDisplayString
- Source
- RFC1213-MIBDisplayString
- Base type
OctetString
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAdvStateAbnormalConditions mandatory An ASCII string containing the 32 flags representing
the current active UPS faults. If the Network Card
is unable to determine the values of the flags, this
variable is set to 'UN… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.1 |
| upsAdvStateNumberoftimesonbattery mandatory Number of times the UPS was on battery.
Since the last reset of statistical data. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.11.2.10 |
| upsAdvStateNumberoftimesbypass mandatory Number of times the UPS was in bypass.
Since the last reset of statistical data. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.11.2.11 |
| upsAdvStateNumberoftimesNormal mandatory Number of times the UPS was in normal operation.
Since the last reset of statistical data. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.11.2.12 |
| upsAdvStateEcomode mandatory Eco mode status.
1: UPS is on Eco-mode
2: UPS is not on Eco-mode. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.11.2.13 |
| upsAdvStateLifeCycleManagement mandatory An ASCII string containing the 16 flags representing the life cycle management alerts
for the device. If the Network Card is unable to determine the values of the flags,
this vari… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.14 |
| upsAdvStateGalaxyVseriesSpecificFault optional An ASCII string containing 32 flags representing
current active faults on a Galaxy V series UPS.
The upsAdvStateAbnormalConditions OID shall be used to report
active faults as per… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.15 |
| upsAdvStateSymmetra3PhaseSpecificFaults mandatory An ASCII string containing the 64 flags representing
the current active UPS specific faults for the Symmetra
3-Phase UPS models. If the Network Card is unable to
determine the val… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.2 |
| upsAdvStateDP300ESpecificFaults mandatory An ASCII string containing the 64 flags representing
the current active UPS specific faults for the Silcon
DP300E UPS models. If the Network Card is unable to
determine the values… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.3 |
| upsAdvStateSymmetraSpecificFaults mandatory An ASCII string containing the 64 flags representing
the current active UPS specific faults for the Symmetra
UPS models. If the Network Card is unable to determine
the values of t… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.4 |
| upsAdvStateSmartUPSSpecificFaults mandatory An ASCII string containing the 64 flags representing
the current active UPS specific faults for the Smart-UPS
UPS models. If the Network Card is unable to determine
the values of … | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.5 |
| upsAdvStateSystemMessages mandatory An ASCII string containing the 3 digit Decimal code
representing the current active message from the
System Message Register. Each code should remain active
for a minimum of 15 se… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.6 |
| upsAdvStateTotaltimeonbattery mandatory Total time the UPS has been in battery operation. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.7 |
| upsAdvStateTotaltimeonbypass mandatory Total time the UPS has been in bypass operation. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.8 |
| upsAdvStateTotaltimeonNormal mandatory Total time the UPS has been in normal operation. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.9 |