upsAdvStateGalaxyVseriesSpecificFault

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.1.11.2.15

Object

scalar optional RFC1213-MIBDisplayString
An ASCII string containing 32 flags representing
current active faults on a Galaxy V series UPS.
The upsAdvStateAbnormalConditions OID shall be used to report
active faults as per its description. Additional fault information
shall be provided through the upsAdvStateGalaxyVseriesSpecificFault OID.
If the Network Card is unable to determine the values of the flags, this
variable is set to 'UNKNOWN'. If this variable is not
supported by the connected UPS, this variable is set to
'NOT SUPPORTED'.
          
The flags are numbered from 1 to 32, and read from left to
right. The flags are defined as follows:
          
Flag  1: Input voltage is out of tolerance
Flag  2: Input frequency is out of tolerance
Flag  3: External sync frequency is out of tolerance
Flag  4: Output frequency is out of tolerance
          
Flag  5: The static bypass switch needs a technical check but is still fully operational
Flag  6: Static bypass switch is inoperable. UPS is prevented from going into static bypass operation
Flag  7: PBUS cable 1 may be damaged
Flag  8: PBUS cable 2 may be damaged
          
Flag  9: The parallel system is not configured correctly or is not working correctly
Flag 10: The UC in the controller box is not working correctly
Flag 11: Power module surveillance detected a fault
Flag 12: The SLC in the controller box is not working correctly
          
Flag 13: No SBS present
Flag 14: No power module(s) present
Flag 15: Controller box disabled
Flag 16: Display communication lost - disconnected
          
Flag 17: The energy storage surveillance has detected a battery temperature above shutdown limit
Flag 18: Modular battery cabinet fuse blown
Flag 19: Battery module temperature sensor not working correctly
Flag 20: The energy storage surveillance has detected a battery discharge current above shutdown limit
          
Flag 21: Ground fault detected
Flag 22: External energy storage monitoring: Minor alarm
Flag 23: External energy storage monitoring: Major alarm
Flag 24: Temperature of input and/or output transformer is too high
          
Flag 25: Parallel breaker status inconsistency detected
Flag 26: UC communication lost - disconnected
Flag 27: PMC communication lost - disconnected
Flag 28: NMC communication lost - disconnected
          
Flag 29: BMC communication lost - disconnected
Flag 30: <Reserved>
Flag 31: <Reserved>
Flag 32: <Reserved>

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.1.11.2.15
Type
scalar
Access
readonly
Status
optional
Parent
upsAdvState
Siblings
15

Syntax

RFC1213-MIBDisplayString
Source
RFC1213-MIBDisplayString
Base type
OctetString

Values & Constraints

No enumerated values or constraints recorded.

Related Objects

Sibling Objects