upsAdvStateAbnormalConditions
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.11.2.1
Object
An ASCII string containing the 32 flags representing
the current active UPS faults. If the Network Card
is unable to determine the values of the flags, this
variable is set to 'UNKNOWN'. If this variable is not
supported by the connected UPS, this variable is set to
'NOT SUPPORTED'.
The flags are numbered from 1 to 32, and read from left to
right. The flags are defined as follows:
Flag 1: Power Module Failure
Flag 2: Main Intelligence Module Failure
Flag 3: Redundant Intelligence Module Failure
Flag 4: Battery Failure
Flag 5: Load(kVA) Alarm Threshold Violation
Flag 6: Redundancy Lost
Flag 7: Redundancy Below Alarm Threshold
Flag 8: Bypass not in Range; Either Frequency or Voltage
Flag 9: Bypass Contactor Stuck in Bypass Condition
Flag 10: Bypass Contactor Stuck in On-Line Condition
Flag 11: In Bypass due to an Internal Fault
Flag 12: In Bypass due to an Overload
Flag 13: In Maintenance Bypass
Flag 14: Input Circuit Breaker Tripped Open
Flag 15: System Level Fan Failure
Flag 16: Redundant Intelligent Module in Control
Flag 17: IIC Inter-Module Communication Failure
Flag 18: No Working Power Modules
Flag 19: Load Shutdown From Bypass; Input Frequency
Flag 20: Runtime Below Alarm Threshold
Flag 21: Extended Run Frame Fault
Flag 22: Output Voltage out of Range
Flag 23: UPS Not Synchronized
Flag 24: No Batteries Installed
Flag 25: Battery Voltage High
Flag 26: UPS Specific Fault Detected
Flag 27: Site Wiring Fault
Flag 28: Backfeed Protection Relay Opened
Flag 29: EPO (Emergency Power Off) switch is activated
Flag 30: UPS surveillance has detected a fault
Flag 31: System overload detected or short circuit detected on the output
Flag 32: Ambient temperature is out of tolerance
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.11.2.1- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- upsAdvState
- Siblings
- 15
Syntax
RFC1213-MIBDisplayString
- Source
- RFC1213-MIBDisplayString
- Base type
OctetString
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAdvStateNumberoftimesonbattery mandatory Number of times the UPS was on battery.
Since the last reset of statistical data. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.11.2.10 |
| upsAdvStateNumberoftimesbypass mandatory Number of times the UPS was in bypass.
Since the last reset of statistical data. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.11.2.11 |
| upsAdvStateNumberoftimesNormal mandatory Number of times the UPS was in normal operation.
Since the last reset of statistical data. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.11.2.12 |
| upsAdvStateEcomode mandatory Eco mode status.
1: UPS is on Eco-mode
2: UPS is not on Eco-mode. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.11.2.13 |
| upsAdvStateLifeCycleManagement mandatory An ASCII string containing the 16 flags representing the life cycle management alerts
for the device. If the Network Card is unable to determine the values of the flags,
this vari… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.14 |
| upsAdvStateGalaxyVseriesSpecificFault optional An ASCII string containing 32 flags representing
current active faults on a Galaxy V series UPS.
The upsAdvStateAbnormalConditions OID shall be used to report
active faults as per… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.15 |
| upsAdvStateGutorModularSpecificFaults optional An ASCII string containing the 64 flags representing
the current active Charger Rectifier and UPS specific faults for Gutor Modular models.
Flag allocation:
Flag 1 to 16 for break… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.16 |
| upsAdvStateSymmetra3PhaseSpecificFaults mandatory An ASCII string containing the 64 flags representing
the current active UPS specific faults for the Symmetra
3-Phase UPS models. If the Network Card is unable to
determine the val… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.2 |
| upsAdvStateDP300ESpecificFaults mandatory An ASCII string containing the 64 flags representing
the current active UPS specific faults for the Silcon
DP300E UPS models. If the Network Card is unable to
determine the values… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.3 |
| upsAdvStateSymmetraSpecificFaults mandatory An ASCII string containing the 64 flags representing
the current active UPS specific faults for the Symmetra
UPS models. If the Network Card is unable to determine
the values of t… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.4 |
| upsAdvStateSmartUPSSpecificFaults mandatory An ASCII string containing the 64 flags representing
the current active UPS specific faults for the Smart-UPS
UPS models. If the Network Card is unable to determine
the values of … | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.5 |
| upsAdvStateSystemMessages mandatory An ASCII string containing the 3 digit Decimal code
representing the current active message from the
System Message Register. Each code should remain active
for a minimum of 15 se… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.6 |
| upsAdvStateTotaltimeonbattery mandatory Total time the UPS has been in battery operation. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.7 |
| upsAdvStateTotaltimeonbypass mandatory Total time the UPS has been in bypass operation. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.8 |
| upsAdvStateTotaltimeonNormal mandatory Total time the UPS has been in normal operation. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.11.2.9 |