upsAdvInputDCVoltage
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.3.2.16
Object
scalar
mandatory
Integer32
The DC input voltage in Volts.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.3.2.16- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- upsAdvInput
- Siblings
- 17
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAdvInputLineVoltage mandatory The current utility line voltage in VAC. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.318.1.1.1.3.2.1 |
| upsAdvInputStatisticsTable mandatory A list of input table entries. The number of entries
is given by the value of upsPhaseNumInputs. | table | - | .1.3.6.1.4.1.318.1.1.1.3.2.10 |
| upsAdvInputTotalApparentPower mandatory The input total apparent power(sum of all three phases)
of the UPS system in kVA. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.3.2.11 |
| upsAdvInputTotalActivePower mandatory The input total active power(sum of all three phases) of the UPS system in kW.
If not supported, return -1 | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.3.2.12 |
| upsAdvInputBypassTotalApparentPower mandatory The input bypass total apparent power(sum of all three phases)
of the UPS system in kVA. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.3.2.13 |
| upsAdvInputBypassTotalActivePower mandatory The input bypass total active power(sum of all three phases)
of the UPS system in kW. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.3.2.14 |
| upsAdvInputEnergyUsage mandatory The input energy usage of the UPS in kWh. | scalar | Unsigned32 | .1.3.6.1.4.1.318.1.1.1.3.2.15 |
| upsAdvInputDCCurrent mandatory The DC input current in Amps. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.3.2.17 |
| upsAdvInputNominalDCVoltage mandatory The nominal input DC voltage of the inverter in Volts.
If not supported, return -1. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.3.2.18 |
| upsAdvInputMaxLineVoltage mandatory The maximum utility line voltage in VAC over the
previous 1 minute period. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.318.1.1.1.3.2.2 |
| upsAdvInputMinLineVoltage mandatory The minimum utility line voltage in VAC over the
previous 1 minute period. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.318.1.1.1.3.2.3 |
| upsAdvInputFrequency mandatory The current input frequency to the UPS system in Hz. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.318.1.1.1.3.2.4 |
| upsAdvInputLineFailCause mandatory The reason for the occurrence of the last transfer to UPS
battery power. The variable is set to:
- noTransfer(1) -- if there is no transfer yet.
- highLineVoltage(2) -- if the tr… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.3.2.5 |
| upsAdvInputNominalFrequency mandatory The nominal input frequency of the UPS system in Hz. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.3.2.6 |
| upsAdvInputNominalVoltage mandatory The nominal input voltage of the UPS system in VAC. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.3.2.7 |
| upsAdvInputBypassNominalFrequency mandatory The nominal bypass input frequency of the UPS system in Hz. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.3.2.8 |
| upsAdvInputBypassNominalVoltage mandatory The nominal bypass input voltage of the UPS system in VAC. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.1.3.2.9 |