upsAdvControlUpsSleep
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.6.2.3
Object
scalar
mandatory
r/w
Enumeration
Setting this variable to putUpsToSleep(2) causes
the UPS to go to sleep for the time specified by
upsAdvConfigUpsSleepTime.
Setting this variable to putUpsToSleepGracefully(3)
causes the UPS to go to sleep for the time specified
by upsAdvConfigUpsSleepTime after a delay period.
This allows the host to shut down in a graceful manner.
If this UPS is an active member of a Synchronized Control
Group (SCG), the putUpsSyncGroupToSleep(4) command will perform
a Synchronized Sleep of all active Group members regardless
of their current AC output status. This unit's Power
Synchronization Delay, Shutdown Delay, Sleep Time,
and Return Delay will be used to execute the sleep command.
If this UPS is an active member of a SCG the
putUpsSyncGroupToSleepGracefully(5) command will perform a
Synchronized Sleep Gracefully of all active Group members
regardless of their current AC output status. This unit's
Power Synchronization Delay, Maximum Shutdown Time, Shutdown
Delay, Sleep Time, and Return Delay to execute the sleep
command.
When in sleep mode, the UPS will not provide output
power regardless of the input line state. Once the
specified time has elapsed, output power will be
restored.
Setting this value to noPutUpsToSleep(1) has no
effect.
The value noPutUpsToSleep(1) will always be returned
when the variable is read.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.6.2.3- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsAdvControl
- Siblings
- 8
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | noPutUpsToSleep |
2 | putUpsToSleep |
3 | putUpsToSleepGracefully |
4 | putUpsSyncGroupToSleep |
5 | putUpsSyncGroupToSleepGracefully |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAdvControlUpsOff mandatory Setting this variable to turnUpsOff(2) causes
the UPS to shut off. When in this state, the UPS
will not provide output power regardless of the input
line state.
Settin… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.1 |
| upsAdvControlRebootShutdownUps mandatory Setting this variable to rebootShutdownUps(2) causes the UPS
to shut off and turn back on (as long as good AC input power
is available, otherwise the UPS will remain off until goo… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.2 |
| upsAdvControlSimulatePowerFail mandatory Setting this variable to simulatePowerFailure(2) causes
the UPS switch to battery power.
Setting this value to noSimulatePowerFailure(1) has no
effect.
The v… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.4 |
| upsAdvControlFlashAndBeep mandatory Setting this variable to flashAndBeep(2) causes the
UPS to beep and simultaneously turn on the UPS front
panel lights (Smart-UPS only).
If this UPS is an active member … | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.5 |
| upsAdvControlTurnOnUPS mandatory Setting this variable to turnOnUPS(2) causes the
UPS to be turned on immediately.
If this UPS is an active member of a Synchronized Control
Group (SCG), the turnOnUPSSy… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.6 |
| upsAdvControlBypassSwitch mandatory This switch puts the UPS in or out of bypass mode. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.7 |
| upsAdvControlRebootUpsWithOrWithoutAC mandatory Setting this variable to rebootUpsImmediatelyWithOrWithoutAC (2)
causes the UPS to turn off immediately, wait for a minimum time
(typically 8 seconds), and then turn back on regar… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.8 |
| upsAdvControlFirmwareUpdate mandatory Setting this variable to firmwareUpdate(2) causes the
UPS to begin a firmware update if possible.
Setting this value to noFirmwareUpdate(1) will clear the
previous resu… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.9 |