upsAdvControlUpsOff
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.6.2.1
Object
scalar
mandatory
r/w
Enumeration
Setting this variable to turnUpsOff(2) causes
the UPS to shut off. When in this state, the UPS
will not provide output power regardless of the input
line state.
Setting this variable to turnUpsOffGracefully(3) causes
the UPS to shut off after a delay period. This allows the
host to shut down in a graceful manner. When in this state,
the UPS will not provide output power regardless of the
input line state.
If this UPS is an active member of a Synchronized
Control Group (SCG) the turnUpsSyncGroupOff(4) command
will perform a Synchronized Turn Off of all active Group
members regardless of their current AC output status.
If this UPS is an active member of a Synchronized
Control Group (SCG) the turnUpsSyncGroupOffAfterDelay(5)
command will perform a Synchronized Turn Off After Delay
of all active Group members regardless of their current
AC output status. This unit's Shutdown Delay will be used
to execute the Turn Off After Delay command.
If this UPS is an active member of an SCG, the
turnUpsSyncGroupOffGracefully(6) command will perform a
Synchronized Turn Off Gracefully of all active Group
members regardless of their current AC output status.
This unit's Maximum Shutdown Time and Shutdown Delay will
be used to execute the Turn Off Gracefully command.
Setting this value to noTurnUpsOff(1) has no
effect.
The value noTurnUpsOff(1) will always be returned
when the variable is read.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.6.2.1- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsAdvControl
- Siblings
- 8
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | noTurnUpsOff |
2 | turnUpsOff |
3 | turnUpsOffGracefully |
4 | turnUpsSyncGroupOff |
5 | turnUpsSyncGroupOffAfterDelay |
6 | turnUpsSyncGroupOffGracefully |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAdvControlRebootShutdownUps mandatory Setting this variable to rebootShutdownUps(2) causes the UPS
to shut off and turn back on (as long as good AC input power
is available, otherwise the UPS will remain off until goo… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.2 |
| upsAdvControlUpsSleep mandatory Setting this variable to putUpsToSleep(2) causes
the UPS to go to sleep for the time specified by
upsAdvConfigUpsSleepTime.
Setting this variable to putUpsToSleepGracef… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.3 |
| upsAdvControlSimulatePowerFail mandatory Setting this variable to simulatePowerFailure(2) causes
the UPS switch to battery power.
Setting this value to noSimulatePowerFailure(1) has no
effect.
The v… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.4 |
| upsAdvControlFlashAndBeep mandatory Setting this variable to flashAndBeep(2) causes the
UPS to beep and simultaneously turn on the UPS front
panel lights (Smart-UPS only).
If this UPS is an active member … | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.5 |
| upsAdvControlTurnOnUPS mandatory Setting this variable to turnOnUPS(2) causes the
UPS to be turned on immediately.
If this UPS is an active member of a Synchronized Control
Group (SCG), the turnOnUPSSy… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.6 |
| upsAdvControlBypassSwitch mandatory This switch puts the UPS in or out of bypass mode. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.7 |
| upsAdvControlRebootUpsWithOrWithoutAC mandatory Setting this variable to rebootUpsImmediatelyWithOrWithoutAC (2)
causes the UPS to turn off immediately, wait for a minimum time
(typically 8 seconds), and then turn back on regar… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.8 |
| upsAdvControlFirmwareUpdate mandatory Setting this variable to firmwareUpdate(2) causes the
UPS to begin a firmware update if possible.
Setting this value to noFirmwareUpdate(1) will clear the
previous resu… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.9 |