upsAdvControlFirmwareUpdate
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.6.2.9
Object
scalar
mandatory
r/w
Enumeration
Setting this variable to firmwareUpdate(2) causes the
UPS to begin a firmware update if possible.
Setting this value to noFirmwareUpdate(1) will clear the
previous results, if any, or otherwise has no effect.
Reading this variable will return noFirmwareUpdate(1) when
the UPS firmware has not been updated (or previous results
have been cleared), updateInProcess(3) when the UPS firmware
is being updated, updateSuccessful(4) when the UPS firmware
has been successfully updated, or updateFailed(5) if the UPS
firmware update failed.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.6.2.9- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsAdvControl
- Siblings
- 8
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | noFirmwareUpdate |
2 | firmwareUpdate |
3 | updateInProcess |
4 | updateSuccessful |
5 | updateFailed |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAdvControlUpsOff mandatory Setting this variable to turnUpsOff(2) causes
the UPS to shut off. When in this state, the UPS
will not provide output power regardless of the input
line state.
Settin… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.1 |
| upsAdvControlRebootShutdownUps mandatory Setting this variable to rebootShutdownUps(2) causes the UPS
to shut off and turn back on (as long as good AC input power
is available, otherwise the UPS will remain off until goo… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.2 |
| upsAdvControlUpsSleep mandatory Setting this variable to putUpsToSleep(2) causes
the UPS to go to sleep for the time specified by
upsAdvConfigUpsSleepTime.
Setting this variable to putUpsToSleepGracef… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.3 |
| upsAdvControlSimulatePowerFail mandatory Setting this variable to simulatePowerFailure(2) causes
the UPS switch to battery power.
Setting this value to noSimulatePowerFailure(1) has no
effect.
The v… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.4 |
| upsAdvControlFlashAndBeep mandatory Setting this variable to flashAndBeep(2) causes the
UPS to beep and simultaneously turn on the UPS front
panel lights (Smart-UPS only).
If this UPS is an active member … | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.5 |
| upsAdvControlTurnOnUPS mandatory Setting this variable to turnOnUPS(2) causes the
UPS to be turned on immediately.
If this UPS is an active member of a Synchronized Control
Group (SCG), the turnOnUPSSy… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.6 |
| upsAdvControlBypassSwitch mandatory This switch puts the UPS in or out of bypass mode. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.7 |
| upsAdvControlRebootUpsWithOrWithoutAC mandatory Setting this variable to rebootUpsImmediatelyWithOrWithoutAC (2)
causes the UPS to turn off immediately, wait for a minimum time
(typically 8 seconds), and then turn back on regar… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.1.6.2.8 |