upsAdvConfigReturnDelay

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.1.5.2.9

Object

scalar mandatory r/w RFC1155-SMITimeTicks
The delay in seconds after utility line power returns
before the UPS will turn on.  This value is also used
when the UPS comes out of a reboot and before the UPS
wakes up from 'sleep' mode.
          
For a list of allowed values supported by your UPS model,
see the UPS User's Manual.
          
If a value other than a supported value is provided in a
set request, the UPS interprets it as the next higher
acceptable value.  If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.1.5.2.9
Type
scalar
Access
readwrite
Status
mandatory
Parent
upsAdvConfig
Siblings
79

Syntax

RFC1155-SMITimeTicks
Source
RFC1155-SMITimeTicks
Base type
Unsigned32

Values & Constraints

Type Constraints
range: 0..4294967295

Related Objects

Sibling Objects