upsAdvConfigChargerRate

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.1.5.2.48

Object

scalar mandatory r/w Integer32
Change the maximum allowed UPS charge rate on select products where 100% represents
the manufacturer's recommended rate.  A charge/discharge rate of C/10 for a 10 Ah
battery would be 1 where C is defined as the charge or discharge rate equal to the
capacity of a battery divided by 1 hour. To increase the charge rate by a factor of
2 to C/5, this oid would be set to 200%.  This number would not change when external
packs are added or removed.  Charging at too high a rate can result in boiling and/or
venting of electrolyte and/or high gas pressure.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.1.5.2.48
Type
scalar
Access
readwrite
Status
mandatory
Parent
upsAdvConfig
Siblings
79

Syntax

Integer32
Source
COPS-PR-SPPIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647

Related Objects

Sibling Objects