upsAdvConfigBatteryTemperatureCompensation

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.1.5.2.53

Object

scalar mandatory r/w Integer32
Configure the battery temperature compensation voltage in
hundreds of volts per degree C. On products which support this
field, the charger voltage is reduced for each degree C rise
by the value configured in this setting multiplied by the
number of battery cells attached to the UPS.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.1.5.2.53
Type
scalar
Access
readwrite
Status
mandatory
Parent
upsAdvConfig

Syntax

Integer32

Values & Constraints

No enumerated values or constraints recorded.