upsAdvConfigBatteryTemperatureCompensation
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.5.2.53
Object
scalar
mandatory
r/w
Integer32
Configure the battery temperature compensation voltage in hundreds of volts per degree C. On products which support this field, the charger voltage is reduced for each degree C rise by the value configured in this setting multiplied by the number of battery cells attached to the UPS.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.5.2.53- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsAdvConfig
Syntax
Integer32
Values & Constraints
No enumerated values or constraints recorded.