sPDUMasterControlSwitch
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.4.2.1
Object
scalar
mandatory
r/w
Enumeration
Setting this OID to turnAllOnNow (1) will turn all outlets
on immediately.
Setting this OID to turnAllOnSequence (2) will turn all outlets
on as defined by each outlet's sPDUOutletPowerOnTime OID value.
Setting this OID to turnAllOff (3) will turn all outlets
off immediately.
Setting this OID to rebootAllNow (4) will reboot all outlets
immediately.
For MasterSwitch firmware version 1.X, setting this OID to
rebootAllSequence (5) reboots all outlets, with power returned
to the outlets in the sequence defined by each outlet's
sPDUOutletPowerOnTime OID value.
For MasterSwitch firmware version 2.X, setting this OID to
rebootAllSequence (5) will cause a turnAllOffSequence to be performed.
Once all outlets are off, the MasterSwitch will then delay the
sPDUMasterConfigReboot OID time, and then perform a turnAllOnSequence.
For MasterSwitch firmware version 2.X, setting this OID to
turnAllOffSequence (7) will turn all outlets off as defined by
each outlet's sPDUOutletPowerOffTime OID value.
For MasterSwitch firmware version 1.X, setting this OID to
turnAllOffSequence (7) will have no effect.
Getting this OID will return the noCommand (6) value.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.4.2.1- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- sPDUMasterControl
- Siblings
- 2
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | turnAllOnNow |
2 | turnAllOnSequence |
3 | turnAllOffNow |
4 | rebootAllNow |
5 | rebootAllSequence |
6 | noCommand |
7 | turnAllOffSequence |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| sPDUMasterState mandatory Getting this OID will cause the status of all outlets to be
returned. This OID is provided for informational purposes only.
To change the outlet state, the user should use the sPD… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.4.2.2 |
| sPDUMasterPending mandatory Getting this OID will cause the command pending status of all outlets to be returned.
The format of the data returned is a character string consisting
of the word 'Yes'… | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.4.2.3 |