sPDUMasterControlSwitch

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.4.2.1

Object

scalar mandatory r/w Enumeration
Setting this OID to turnAllOnNow (1) will turn all outlets
on immediately.
          
Setting this OID to turnAllOnSequence (2) will turn all outlets
on as defined by each outlet's sPDUOutletPowerOnTime OID value.
          
Setting this OID to turnAllOff (3) will turn all outlets
off immediately.
          
Setting this OID to rebootAllNow (4) will reboot all outlets
immediately.
          
For MasterSwitch firmware version 1.X, setting this OID to
rebootAllSequence (5) reboots all outlets, with power returned
to the outlets in the sequence defined by each outlet's
sPDUOutletPowerOnTime OID value.
          
For MasterSwitch firmware version 2.X, setting this OID to
rebootAllSequence (5) will cause a turnAllOffSequence to be performed.
Once all outlets are off, the MasterSwitch will then delay the
sPDUMasterConfigReboot OID time, and then perform a turnAllOnSequence.
          
For MasterSwitch firmware version 2.X, setting this OID to
turnAllOffSequence (7) will turn all outlets off as defined by
each outlet's sPDUOutletPowerOffTime OID value.
          
For MasterSwitch firmware version 1.X, setting this OID to
turnAllOffSequence (7) will have no effect.
          
Getting this OID will return the noCommand (6) value.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.4.2.1
Type
scalar
Access
readwrite
Status
mandatory
Parent
sPDUMasterControl
Siblings
2

Syntax

Enumeration

Values & Constraints

Enumerated Values
1turnAllOnNow
2turnAllOnSequence
3turnAllOffNow
4rebootAllNow
5rebootAllSequence
6noCommand
7turnAllOffSequence