sPDUMasterConfigPowerOn
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.4.3.1
Object
scalar
mandatory
r/w
Integer32
The amount of delay, in seconds, between when
power is provided to the PDU and when the PDU
provides basic master power to the outlets.
Allowed values are:
-1 never apply power automatically.
0 apply power immediately.
15 apply power in 15 seconds.
30 apply power in 30 seconds.
45 apply power in 45 seconds.
60 apply power in 60 seconds (1 minute).
120 apply power in 120 seconds (2 minutes).
300 apply power in 300 seconds (5 minutes).
If a value other than a supported value is provided in a
set request, the PDU interprets it as the next lower
acceptable value. If the provided value is lower than
the lowest acceptable value, the lowest acceptable
value is used.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.4.3.1- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- sPDUMasterConfig
- Siblings
- 2
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| sPDUMasterConfigReboot mandatory During a reboot sequence, power is turned off and then
back on. This OID defines the amount of time to wait,
in seconds, after turning the power off, at the start
of the sequence,… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.4.3.2 |
| sPDUMasterConfigPDUName mandatory The name of the PDU. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.4.3.3 |