rPDUOutletDevCommand
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.12.3.1.1
Object
scalar
mandatory
r/w
Enumeration
Setting this OID to immediateAllOn (2) will turn all outlets
on immediately.
Setting this OID to immediateAllOff (3) will turn all outlets
off immediately.
Setting this OID to immediateAllReboot (4) will reboot all outlets
immediately.
Setting this OID to delayedAllOn (5) will turn all outlets on as
defined by each outlet's rPDUOutletConfigPowerOnTime OID value.
Setting this OID to delayedAllOff (6) will turn all outlets
off as defined by each outlet's rPDUOutletConfigPowerOffTime OID value.
Setting this OID to delayedAllReboot (7) will cause a
delayedAllOff command to be performed. Once all outlets are off,
the Switched Rack PDU will then delay the largest
rPDUOutletConfigRebootDuration OID time, and then perform a
delayedAllOn command.
Setting this OID to cancelAllPendingCommands (8) will cause all pending
commands on the Switched Rack PDU to be canceled.
Getting this OID will return the noCommandAll (1) value.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.12.3.1.1- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- rPDUOutletDevice
- Siblings
- 4
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | noCommandAll |
2 | immediateAllOn |
3 | immediateAllOff |
4 | immediateAllReboot |
5 | delayedAllOn |
6 | delayedAllOff |
7 | delayedAllReboot |
8 | cancelAllPendingCommands |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDUOutletDevColdstartDelay mandatory The amount of delay, in seconds, between when
power is provided to the Switched Rack PDU and
when the Switched Rack PDU provides basic master
power to the outlets.
Allo… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.3.1.2 |
| rPDUOutletDevNumCntrlOutlets mandatory The number of controlled outlets on this Switched Rack PDU. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.3.1.3 |
| rPDUOutletDevNumTotalOutlets mandatory The total number of outlets on this Rack PDU. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.3.1.4 |
| rPDUOutletDevMonitoredOutlets mandatory The total number of monitored outlets on this Rack PDU. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.3.1.5 |