rPDULoadDevMaxBankLoad
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.12.2.1.3
Object
scalar
mandatory
Integer32
Getting this OID will return the maximum rated power
that a bank of the Rack PDU can provide. It is
represented in Amps.
0 will be returned if the device does not have any banks.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.12.2.1.3- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- rPDULoadDevice
- Siblings
- 7
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDULoadDevMaxPhaseLoad mandatory Getting this OID will return the maximum rated power
that each phase of the Rack PDU can provide. It is
represented in Amps.
0 will be returned if the unit is banked. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.2.1.1 |
| rPDULoadDevNumPhases mandatory The number of phases available with this Rack PDU. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.2.1.2 |
| rPDULoadDevNumBanks mandatory The number of banks of outlets available with this Rack PDU.
A bank of outlets has a unique circuit breaker for a subset
of the total number of outlets on the rPDU.
0 w… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.2.1.4 |
| rPDULoadDevBankTableSize mandatory The size of the Bank Table. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.2.1.5 |
| rPDULoadDevBankTable mandatory Allows for getting the Bank Max Load in the Rack PDU. | table | - | .1.3.6.1.4.1.318.1.1.12.2.1.6 |
| rPDULoadDevMaxOutletTableSize mandatory The size of the Outlet Table. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.2.1.7 |
| rPDULoadDevMaxOutletTable mandatory Allows for getting the Max Outlet Load in an Outlet Monitored Rack PDU. | table | - | .1.3.6.1.4.1.318.1.1.12.2.1.8 |