rPDUIdentDeviceOutletLayout
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.12.1.13
Object
scalar
mandatory
Enumeration
Getting this OID will return outlet layout for the device.
seqPhaseToNeutral(1) indicates outlet layout as follows:
1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,...
seqPhaseToPhase(2) indicates outlet layout as follows:
1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,...
seqPhToNeu21PhToPh(3) indicates outlet layout as follows:
1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,...
seqPhToPhGrouped(4) indicates outlet layout as follows:
For AP8xxx SKU's Group 1:1-2, Group 2:2-3, Group 3:3-1.
For AP7xxx SKU's Group 1:3-1. Group 2:2-3, Group 3:1-2.
seqPhToNGrouped(5) indicates outlet layout as follows:
This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N.
seqPToN1516PToPGrouped(6) indicates outlet layout as follows:
This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2,
Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1.
seqPhToPh2xGrouped(7) indicates outlet layout as follows:
This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3,
Group 4:2-3, Group 5:3-1, Group 6:3-1.
seqPhToN2xGrouped(8) indicates outlet layout as follows:
This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N,
Group 4:2-N, Group 5:3-N, Group 6:3-N.
seqNotApplicable(9):
Outlet layout does not affect any of the user interfaces.
These SKUs may report seqNotApplicable(9) if there is
not an exact outlet layout match available.
Only AP7xxx, AP8xxx SKUs support this feature.
Product which does not support this feature will respond to this OID
with a value of -1.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.12.1.13- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- rPDUIdent
- Siblings
- 18
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | seqPhaseToNeutral |
2 | seqPhaseToPhase |
3 | seqPhToNeu21PhToPh |
4 | seqPhToPhGrouped |
5 | seqPhToNGrouped |
6 | seqPToN1516PToPGrouped |
7 | seqPhToPh2xGrouped |
8 | seqPhToN2xGrouped |
9 | seqNotApplicable |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDUIdentName mandatory The name of the Rack PDU.
The maximum string size is device dependent. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.12.1.1 |
| rPDUIdentDeviceNumBreakers mandatory Getting this OID will return the number of circuit breakers supported by the device.
This is the same as the number of banks of outlets.
0 will be returned if the unit has no phas… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.1.10 |
| rPDUIdentDeviceBreakerRating mandatory Getting this OID will return rating of the circuit breakers
on the device in Amps if it has any. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.1.11 |
| rPDUIdentDeviceOrientation mandatory Getting this OID will return the intended physical orientation of the device.
OrientHorizonatal(1) indicates Horizontal.
OrientVertical(2) indicates Vertical. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.12.1.12 |
| rPDUIdentDeviceDisplayOrientation mandatory Getting this OID will return the intended physical orientation of the Seven-Segment Display
or LCD.
Normal(1) indicates Normal.
Reverse(2)indicates Upside-Down. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.12.1.14 |
| rPDUIdentDeviceLinetoLineVoltage mandatory Getting/Setting this OID will return/set the Line to Line Voltage.
This OID defaults to the nominal input line voltage in volts AC.
This setting is used to calculate total power a… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.1.15 |
| rPDUIdentDevicePowerWatts mandatory Getting this OID will return the Power in Watts. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.1.16 |
| rPDUIdentDevicePowerFactor mandatory Getting/setting this OID will return/set the
Power Factor in thousandths (1000 is power factor of 1).
This OID is only writable for AP7xxx SKUs
Valid range is from 0 to… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.1.17 |
| rPDUIdentDevicePowerVA mandatory Getting this OID will return the Power in VA. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.1.18 |
| rPDUIdentDeviceLinetoNeutralVoltage mandatory Getting/Setting this OID will return/set the Line to Neutral Voltage.
This OID defaults to the nominal line to neutral voltage in volts AC.
This setting is used to calculate total… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.1.19 |
| rPDUIdentHardwareRev mandatory The hardware revision of the Rack PDU.
This value is set at the factory. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.12.1.2 |
| rPDUIdentFirmwareRev mandatory An 8-byte ID string identifying the Rack PDU firmware revision.
This value is set at the factory. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.12.1.3 |
| rPDUIdentDateOfManufacture mandatory The date when the Rack PDU was manufactured in mm/dd/yyyy format.
This value is set at the factory. The year 2000 will be
represented by 00. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.12.1.4 |
| rPDUIdentModelNumber mandatory A 10-character string identifying the model number of
the Rack PDU. This value is set at the factory. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.12.1.5 |
| rPDUIdentSerialNumber mandatory A 12-character string identifying the serial number of
the Rack PDU. This value is set at the factory. | scalar | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.12.1.6 |
| rPDUIdentDeviceRating mandatory Getting this OID will return the electrical rating of the device in Amps. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.1.7 |
| rPDUIdentDeviceNumOutlets mandatory Getting this OID will return the number of outlets contained in the device. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.1.8 |
| rPDUIdentDeviceNumPhases mandatory Getting this OID will return the number of phases supported by the device. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.12.1.9 |