rPDUIdentDeviceLinetoLineVoltage

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.12.1.15

Object

scalar mandatory r/w Integer32
Getting/Setting this OID will return/set the Line to Line Voltage.
This OID defaults to the nominal input line voltage in volts AC.
This setting is used to calculate total power and must be configured for best accuracy.
Only AP7xxx SKUs support this feature.
The valid range is between 0V to 440V

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.12.1.15
Type
scalar
Access
readwrite
Status
mandatory
Parent
rPDUIdent

Syntax

Integer32

Values & Constraints

No enumerated values or constraints recorded.