isxModularDistSysCurrentThresholdHigh

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.22.4.2.5

Object

scalar mandatory r/w Integer32
When total system current in any phase exceeds this value a warning alarm will exist.
Specified as a percent of the panel rating, isxModularDistSysCurrentRating.
A value of -1 indicates that the threshold is not available in the device.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.22.4.2.5
Type
scalar
Access
readwrite
Status
mandatory
Parent
isxModularDistSysCurrent
Siblings
10

Syntax

Integer32
Source
COPS-PR-SPPIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647