dm3ConfigSysLowTempAlarm
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.7.2.1.6
Object
scalar
mandatory
r/w
Enumeration
For the System Low Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.7.2.1.6- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- dm3ConfigSystem
- Siblings
- 7
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | alarmIgnore |
2 | alarmRelay1 |
3 | alarmRelay2 |
4 | alarmRelay3 |
5 | alarmRelay4 |
6 | alarmRelay5 |
7 | alarmRelay6 |
8 | alarmMinor |
9 | alarmMajor |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| dm3ConfigSysDescriptionTableSize mandatory The number of DC description records. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.1.1 |
| dm3ConfigSysDescriptionTable mandatory Allows for accessing description records of the powerplant. The number of
entries is contained in the dm3ConfigSysDescriptionTableSize OID. | table | - | .1.3.6.1.4.1.318.1.1.7.2.1.2 |
| dm3ConfigSysHighTempThresh mandatory Ambient high temperature threshold. Temperature sensor located on Master
Controller board.
Values are represented in thousandths of a degree.
Units are displayed in th… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.1.3 |
| dm3ConfigSysHighTempAlarm mandatory For the System High Temperature Alarm;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to alarmRelay1 (2) causes relay 1 to be a… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.7.2.1.4 |
| dm3ConfigSysLowTempThresh mandatory Ambient low temperature threshold. Temperature sensor located on Master
Controller board.
Values are represented in thousandths of a degree.
Units are displayed in the… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.7.2.1.5 |
| dm3ConfigSysHardwareTempAlarm mandatory For the System Hardware Temperature Alarm;
Setting this OID to alarmIgnore (1) results in the alarm condition being ignored.
Setting this OID to alarmRelay1 (2) causes relay 1 to … | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.7.2.1.7 |
| dm3ConfigSysRemoteAccess mandatory This OID is used to disable remote write access to the power plant.
Setting this OID to accessEnabled (1) will have no affect.
Setting this OID to accessDisabled (2) will disable … | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.7.2.1.8 |